AXL F PSDO8/3 1F
68
PHOENIX CONTACT
105739_en_04
Safe digital outputs
Quantity
4 two-channel or 8 single-channel (positive switching)
Supply
From supply voltage U
O
Maximum output current per output (channel)
2 A
1.5 A (from 45°C according to CUL
US
)
Maximum output current for all outputs (total current)
8 A
6 A (from 45°C according to CUL
US
)
Maximum output current for each group (total current)
Group 1 (OUT0_K1, OUT1_K1, OUT2_K1, OUT3_K1)
4 A
3 A (from 45°C according to CUL
US
)
Group 2 (OUT0_K2, OUT1_K2, OUT2_K2, OUT3_K2)
4 A
3 A (from 45°C according to CUL
US
)
Maximum output voltage in the low state
< 5 V
Maximum leakage current in the low state
2 mA
Minimum withstand voltage of the connected loads
> 5 V
Maximum inductive load
1 H
Maximum capacitive load
10 µF per channel
10 µF in total
Minimum load
1.5 k
(16 mA at 24 V)
Limitation of the voltage induced on circuit interruption
-15 V
Output voltage
U
O
- 1 V, approximately
Simultaneity
100% up to 45°C (observe maximum current load)
Maximum switching frequency
1 Hz; 0.2 Hz at > 1 A
Filter time
None
Switch-off delay for shutdown according to stop category 1
250 ms / 500 ms / 1 s / 2 s / 4 s / 8 s / 16 s / 32 s / 64 s / 128 s
Accuracy: ±5% of the set value
see Section 5.2 “Parameterization of the safe outputs” on page 34
Maximum duration of the test pulses (when switched off; active driving)
1 ms
WARNING: Loss of safety function
The use of unsuitable power supplies can result in the loss of the safety function.
•
Only use power supplies according to EN 50178/VDE 0160 (PELV) for the voltage supply at the bus coupler.
•
Make sure that the output voltage of the power supply for the bus coupler does not exceed 32 V even in the event of an error.
•
Observe the general safety notes: see Section 1.2 “Electrical safety” on page 10.
WARNING: Loss of safety function
Switching the load at the maximum leakage current can result in the loss of the safety function.
•
Please note that at this current, the load must not switch to or remain in the ON state.
•
Please take this into consideration when selecting the actuator.
WARNING: Loss of safety function
Switching the load at the minimum withstand voltage can result in the loss of the safety function.
•
Please note that at this voltage, the load must not be switched or remain in the ON state.
•
Please take this into consideration when selecting the actuator.
WARNING: Loss of safety function
The switch-on pulse can result in the loss of the safety function.
•
Please note that the load on a switch-on pulse (light test) of 1 ms must not fail or respond in a safety-critical way.
•
Please take this into consideration when selecting the actuator.
Summary of Contents for Axioline F
Page 1: ...User manual Axioline F safety module with safe digital outputs UM EN AXL F PSDO8 3 1F ...
Page 8: ...AXL F PSDO8 3 1F 8 PHOENIX CONTACT 105739_en_04 ...
Page 22: ...AXL F PSDO8 3 1F 22 PHOENIX CONTACT 105739_en_04 ...
Page 32: ...AXL F PSDO8 3 1F 32 PHOENIX CONTACT 105739_en_04 ...
Page 36: ...AXL F PSDO8 3 1F 36 PHOENIX CONTACT 105739_en_04 ...
Page 46: ...AXL F PSDO8 3 1F 46 PHOENIX CONTACT 105739_en_04 ...
Page 50: ...AXL F PSDO8 3 1F 50 PHOENIX CONTACT 105739_en_04 ...
Page 62: ...AXL F PSDO8 3 1F 62 PHOENIX CONTACT 105739_en_04 ...
Page 64: ...AXL F PSDO8 3 1F 64 PHOENIX CONTACT 105739_en_04 ...
Page 84: ...AXL F PSDO8 3 1F 84 PHOENIX CONTACT 105739_en_04 ...
Page 86: ...AXL F PSDO8 3 1F 86 PHOENIX CONTACT 105739_en_04 ...