AXL F PSDO8/3 1F
60
PHOENIX CONTACT
105739_en_04
8.2.4
General errors
Table 8-12
General errors
AXIO code
Error cause
LED
Description/effect
Acknowledgment/remedy
0x4210
Critical module
temperature
SD on The module temperature has
reached a critical value. Immediate
shutdown. A further temperature
increase causes the device firmware
to switch the module to the safe
state.
Check ambient conditions and
switching frequency and adjust, if
necessary.
This diagnostic message can be
acknowledged. Acknowledgment
deletes the diagnostic message.
0xA012
Hardware fault or
application on the module
is not ready
FS on Communication to the higher-level
safe controller is disabled. The
module switches to the safe state.
Perform power up.
If an error message is output again,
the module is faulty and must be
replaced.
DIP switch moved during
operation
FS on The module switches to the safe
state.
Check DIP switch position.
Perform power up.
This diagnostic message cannot be
acknowledged.
Summary of Contents for Axioline F
Page 1: ...User manual Axioline F safety module with safe digital outputs UM EN AXL F PSDO8 3 1F ...
Page 8: ...AXL F PSDO8 3 1F 8 PHOENIX CONTACT 105739_en_04 ...
Page 22: ...AXL F PSDO8 3 1F 22 PHOENIX CONTACT 105739_en_04 ...
Page 32: ...AXL F PSDO8 3 1F 32 PHOENIX CONTACT 105739_en_04 ...
Page 36: ...AXL F PSDO8 3 1F 36 PHOENIX CONTACT 105739_en_04 ...
Page 46: ...AXL F PSDO8 3 1F 46 PHOENIX CONTACT 105739_en_04 ...
Page 50: ...AXL F PSDO8 3 1F 50 PHOENIX CONTACT 105739_en_04 ...
Page 62: ...AXL F PSDO8 3 1F 62 PHOENIX CONTACT 105739_en_04 ...
Page 64: ...AXL F PSDO8 3 1F 64 PHOENIX CONTACT 105739_en_04 ...
Page 84: ...AXL F PSDO8 3 1F 84 PHOENIX CONTACT 105739_en_04 ...
Page 86: ...AXL F PSDO8 3 1F 86 PHOENIX CONTACT 105739_en_04 ...