Errors: messages and removal
105739_en_04
PHOENIX CONTACT
57
8.2.1
Safe digital output errors
Table 8-9
Safe digital output errors
AXIO code
Error cause
LED
Description/effect
Acknowledgment/remedy
0x2370
Cross-circuit between
two outputs
SD
on
All
OUT:
red
on
A cross-circuit with another output or
an external voltage has been
detected. As a result all outputs are
kept in the safe state.
Read channel number via
DiagStateChannelNo object 0x033.
Check actuator, check connector
and cabling.
This diagnostic message can be
acknowledged. Acknowledgment
deletes the message and enables
the outputs.
If the error is still present, the
message is output again.
0x2371
Cross-circuit between
external voltage and an
output
0x2344
Short circuit or overload
at the indicated output
SD
on
OUT:
red
on
A short circuit or overload has been
detected at the indicated output. As
a result the affected output is kept in
the safe state.
Read channel number via
DiagStateChannelNo object 0x033.
Check actuator, check connector
and cabling, check freewheeling
circuit at the contactor.
This diagnostic message can be
acknowledged. Acknowledgment
deletes the message and enables
the outputs.
Following successful
acknowledgment, the safe module
also expects a positive edge from the
application for the output to be
switched. For two-channel
parameterization, this also applies to
the other, potentially error-free
output.
0x8F08
Light test error at the
indicated output
SD
on
All
OUT:
red
on
An error has been detected at the
indicated output by the test pulses
(brief activation). As a result all
outputs are kept in the safe state. A
possible cause may also be a short-
circuit event in the external wiring
during the test.
Read channel number via
DiagStateChannelNo object 0x033.
This diagnostic message can be
acknowledged. Acknowledgment
deletes the message and enables
the outputs.
0x8F09
Dark test error at the
indicated output
SD
on
All
OUT:
red
on
An error has been detected at the
indicated output by the test pulses
(brief deactivation). As a result all
outputs are kept in the safe state.
Read channel number via
DiagStateChannelNo object 0x033.
This diagnostic message can be
acknowledged. Acknowledgment
deletes the message and enables
the outputs.
The error may need to be
acknowledged several times.
Summary of Contents for Axioline F
Page 1: ...User manual Axioline F safety module with safe digital outputs UM EN AXL F PSDO8 3 1F ...
Page 8: ...AXL F PSDO8 3 1F 8 PHOENIX CONTACT 105739_en_04 ...
Page 22: ...AXL F PSDO8 3 1F 22 PHOENIX CONTACT 105739_en_04 ...
Page 32: ...AXL F PSDO8 3 1F 32 PHOENIX CONTACT 105739_en_04 ...
Page 36: ...AXL F PSDO8 3 1F 36 PHOENIX CONTACT 105739_en_04 ...
Page 46: ...AXL F PSDO8 3 1F 46 PHOENIX CONTACT 105739_en_04 ...
Page 50: ...AXL F PSDO8 3 1F 50 PHOENIX CONTACT 105739_en_04 ...
Page 62: ...AXL F PSDO8 3 1F 62 PHOENIX CONTACT 105739_en_04 ...
Page 64: ...AXL F PSDO8 3 1F 64 PHOENIX CONTACT 105739_en_04 ...
Page 84: ...AXL F PSDO8 3 1F 84 PHOENIX CONTACT 105739_en_04 ...
Page 86: ...AXL F PSDO8 3 1F 86 PHOENIX CONTACT 105739_en_04 ...