RFC 4072R
114 / 128
PHOENIX CONTACT
110146_en_00
14.2 Technical data
Dimensions (nominal sizes in mm)
External dimensions (Width x Height x Depth)
122 mm x 182 mmx 173 mm (without fan module)
122 mm x 220 mmx 173 mm (With fan module)
General data
Weight
2730 g (Without fan module)
2960 g (With fan module)
Type
Stand-alone
Mounting type
DIN rail mounting
Module classification
PROFINET controller
Operating system
Yocto/Linux
Processor
Intel
®
Core™ i5-6300U 2x 2.4 GHz (Standard)
Flash memory
100 Mbyte (internal flash memory)
SD card from Phoenix Contact (for external flash memory, see
accessories)
Application interface
OPC UA
OPC UA Pub/Sub
Realtime clock
integrated (capacitive buffering)
Diagnostics display
yes
Controller redundancy
yes
External memory
yes
Web server
yes
Optical interface
yes
Safety function
No
Display
Display type
8,9 cm / 3,5"-TFT
Touch technology
Analog resistive, single-touch control
Display formats
4:3
Screen resolution
240 x 320 Pixel(s)
Ambient conditions
Ambient temperature (operation)
0 °C ... 60 °C up to 2000 m above mean sea level (recom
-
mended: above 50°C with fan module)
0 °C ... 55 °C 2000 m to 3000 m above mean sea level (With fan
module only)
0 °C ... 50 °C 3000 m to 4000 m above mean sea level (With fan
module only)
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
5 % ... 95 % (non-condensing)
Air pressure (operation)
60 kPa ... 108 kPa (up to 4000 m above mean sea level)
Air pressure (storage/transport)
58 kPa ... 108 kPa (up to 4500 m above mean sea level)