Wiring

Achieving the specified protection levels on page 10 
is possible if:
•  incoming mains wires are routed first to the

Xtreme SPD and from there on to the driver input.

•  mains wires between the Xtreme SPD and driver

are kept as short as possible.

•  ground wire between the Xtreme SPD and the

luminaire housing / LED module heatsink is kept
as short as possible.

It is therefore not recommended to remotely mount 
the Xtreme SPD such as in a pole or remote 
distribution box. In cases remote mounting is the 
only option, it is necessary to perform additional 
measurements in the luminaire to define the 
maximum achievable protection levels. 

When connecting the Xtreme SPD, it is strongly 
advised to adhere to the following EMC guidelines:
•  keep all wires short
•  keep wiring loop areas small
•  ensure that mains wires are kept separate from

low-voltage signal circuit wires.

Respecting these rules, will minimize the distance 
and wire length between the Xtreme SPD and the 
mains voltage entry point. 

Insulation Class I and Class II luminaires

The main differences between an insulation Class I

 

and insulation Class II luminaire are about its failsafe

 

construction with respect to electrical safety.

In a Class I luminaire, electrical safety is achieved by

 

a combination of basic insulation between live parts

 

and accessible parts and establishing a protective

 

earth connection (PE) to accessible parts (luminaire

 

housing). Luminaire insulation strength is based on

 

basic system insulation requirements.

A Class II luminaire does not have a protective earth.

 

In this case, electrical safety is achieved by providing

 

double or reinforced insulation which are subject to

 

elevated insulation strength requirements.

Per IEC60598-1: 2014 paragraph 4.10.4 the double or 
reinforced insulation in a (Class II) luminaire between 
live and accessible parts is allowed to be bridged 
only by a resistor and/or capacitor. By design, the 
Xtreme Surge Protector I does not meet this 
requirement. 

Therefore, the Xtreme Surge Protector I is not 
suitable for design-in in an Insulation Class II 
luminaire.

 

Wiring in an insulation Class I luminaire

For optimal protection against surges the SPD should 
be connected in the luminaire as shown below.

Correct wiring in an insulation. Class I luminaire

Xtreme

Surge

Protector

1

OLC

LED driver

EQUI

Basic insulated module

Summary of Contents for Xtreme Surge Protector I

Page 1: ...Design in Guide Protect your outdoor luminaires against damaging spikes and transients April 2019 Outdoor SPD Xtreme Surge Protector I ...

Page 2: ...on as solution 7 Mechanical design 8 Casing 8 Installation 8 CAD drawings 8 SPD connections 8 Failure indicator 8 9 9 10 10 11 11 12 12 Electrical design Protection levels Wiring Insulation Class I and Class II luminaires Incorrect wiring Fusing and mains power distribution system Quality Testing Compliance testing during luminaire release and manufacturing Sustainability System disposal 12 12 ...

Page 3: ...rivers www philips com xitanium OEM general info www philips com technology Attention point Do not use damaged or defective contacts or housings Do not use damaged products Do not service the Xtreme Surge Protector when the mains voltage is connected The luminaire manufacturer is responsible for its own luminaire design this has to comply with all relevant safety standards The Xtreme Surge Protect...

Page 4: ...tage electrical installations Installed in an electrical switchboard this device prevents the spread of spikes and transients in electrical installations and protects the loads Type 2 is characterized by an 8 20 µs current wave Type 3 Type 3 is characterized by a combination of voltage waves 1 2 50 µs and current waves 8 20 µs and is intended mainly for local protection of sensitive equipment The ...

Page 5: ...terminals of the driver differential mode as well as between the driver terminals and the luminaire common mode is being built up and an electrical breakdown between mains wiring and the luminaire will occur The resulting surge voltage and surge current of this electrical breakdown can reach critical levels which can destroy the driver and or LED module The path of the surge current can go through...

Page 6: ...e The energy of the voltage surge is returned as a surge current via the Xtreme SPD to ground and eventually back to the cloud As such it will protect both the driver and LED module against damaging surge stress See figure on the left The Xtreme SPD has to be connected to the protective earth connection of the luminaire Please refer to Electrical design for more information 10kV 2 5kV LED Outdoor ...

Page 7: ...find an arrow indicating the mounting position of the product It is important to mount the device with the connection terminals facing downward to prevent any damage resulting from water entering the product CAD drawings 3D CAD drawings are available on www philips com technology or available via your local sales representative SPD connections The Xtreme Surge Protector is equipped with push in co...

Page 8: ...unction of clamped surge current Ic can be found in the datasheet The initial common mode clamping voltage U1 has an extreme short duration approx 100 ns and will be completely absorbed by the driver it will not result in significant surge stress to the connected LED module and can be ignored Warning Before installation or maintenance switch off the power Avoid touching live parts Protection level...

Page 9: ... an insulation Class I and insulation Class II luminaire are about its failsafe construction with respect to electrical safety In a Class I luminaire electrical safety is achieved by a combination of basic insulation between live parts and accessible parts and establishing a protective earth connection PE to accessible parts luminaire housing Luminaire insulation strength is based on basic system ...

Page 10: ...inrush current so luminaire fusing is not affected by the Xtreme SPD In a TN mains power distribution system the neutral conductor N is connected to the earthed star point of a distribution transformer and is either connected to the star point via a separate conductor TN S or it is partly combined with the protective earth conductor TN C TN C S The Protective Earth PE wire is also connected to the...

Page 11: ...minaires as described in clause 1 3 also known as high pot test Due to the nature of the Philips Xtreme SPD I an insulation strength test would automatically result in a failure as the trigger level of the Xtreme Surge Protector I is below the testing voltage In such a case the note described in clause 1 3 allows that the insulation test may be carried out applying 500 VDC for 1 sec with the insul...

Page 12: ...not be liable for any action in reliance thereon The information presented in this document is not intended as any commercial offer and does not form part of any quotation or contract unless otherwise agreed by Signify Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N V All other trademarks are owned by Signify Holding or their respective owners April 2 2019 ...

Reviews: