READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLING THIS FIXTURE
CAUTION: THE ELECTRICAL POWER MUST BE DISCONNECTED BEFORE OPENING THE FIXTURE
FAILURE TO FOLLOW THE INSTALLATION DOCUMENTATION OR OPERATING THIS PRODUCT
OTHERWISE THAN FOR ITS INTENDED USE VOIDS THE WARRANTY
1/2
442100171450-REV0
RFS/RFM/RFL
ROADFOCUS
INSTALLATIONINSTRUCTIONS
±5°
IMPORTANT: Install the bird guard for ø1.9" or ø1.66" OD tenons
FAILURE TO DO SO VOIDS THE WARRANTY
For ø1.9" tenon, unfold the bird guard
as shown and break away the smaller
diameter lid at the folding line
L
N
RFM
RFS
RFL
1. Push the latch to release the access door
2. Install the bird guard for ø1.9'' or ø1.66'' OD tenons before
sliding the fixture onto the tenon. See the important note below
3. Disconnect power and slide the fixture onto the tenon. See table for
approximate penetration. Horizontal angle can be adjusted in 2.5° steps
4. Evenly tighten the two bolts (4 on RFL)
of the bracket. IMPORTANT: Tighten the
two bolts at 135 lbs.in (11.25 lbs.ft)
5. Connect the service leads to the
terminal block. Tighten the
set-screws between 20 and 25 lbs.in
To change the
orientation of the
socket, loosen the
two screws, orient
it and tighten both
screws
2
1
Latch
A shorting cap, photo control
or other compatible device
must be installed
Tenon
Access door
Bird guard
installed location
If required, place
the supplied
ANSI sticker as
shown
Tenon
5
3 poles
Terminal Block
2-14 AWG
4
3
Tighten the two bolts
(four bolts on RFL)
@ 135 lbs.in (11.25 lbs.ft)
5°
0°
-5°
7"
6.5"
6.2"
5.9"
5.5"
TENON
PENETRATION
RFL
4"
4.5"
4.8"
5"
5.5"
5°
2.5°
0°
-2.5°
-5°
RFS/RFM
ANGLE
FAWS
(option)
Bubble
Level