background image

OccuSwitch Classic 

LRM2376 

 

 

 

Installation and 

Programming Guide 

The Philips OccuSwitch Classic Self-
Contained Daylighting Occupancy Sensor 
offers Passive Infrared (PIR) occupancy 
detection and photocell control of             
0-10VDC dimmable ballasts. The LRM2376 
is an effective solution for areas where both 
occupancy and daylight need to be 
considered in the control scenario. With an 
integrated line switching relay, this sensor is 
perfect for applications where locating a 
power pack is difficult, such as retrofitting 
rooms with concrete or inaccessible 
ceilings. The sensor is line powered, 
switches line voltage, and requires no field 
calibration or sensitivity adjustments. 

Field of View 

Mounting 

• 

Sensor’s mounting holes align with 3.5” 
octagon or single gang handy box (screws 
not provided). 

• 

Sensor will detect motions crossing 
segments more effectively than motions 
parallel to beams. 

• 

For optimal detection, position sensor 
such that segments are crossed upon 
entrance and unable to view outside the 
space. 

Wiring 

Turn OFF breaker of all circuits involved. Wiring the 
device with power ON could result in serious injury 
or death. 

Danger 

Parts of the sensor carry line power, which 
is a potential lethal voltage. This product 
was designed and manufactured to ensure 
maximum safety during operation and 
service.  Always read these safety 
instructions before installing, maintaining or 
servicing the product, and strictly comply 
with these instructions. 

- This product should be installed by a 
qualified electrician. 

- This device is designed for indoor use 
only.  

- Disconnect power at circuit breaker or 
fuse when servicing, installing or removing. 

- Only use with copper or copper clad wire. 

- Wire sensor to the line power according 
to the wiring scheme in this guide.  

- To avoid short circuits, do not expose this 
product to rain or condensing moisture.  
Short circuit may cause fire or electric 
shock hazard.  Operate the devices 
between 14°F to 160°F (-10°C to 71°C) 
ambient temperature.  

It is the installer’s responsibility to ensure that the 
equipment being controlled is visible from every 
control location and that only suitable equipment is 
connected to these controls. Failure to do so could 
result in serious injury or death. 
 
The product is intended to control lighting loads.  Do 
NOT use to control equipment that could create 
hazardous situations, like entrapment.  For examples, 
do NOT install this product to control motorized 
gates, garage doors, industrial doors, microwave 
ovens, heating devices, etc.  

Warning 

Initial Turn ON for all models 

The sensor’s relays are shipped in a latched closed position so the lights will come on upon initial 
power-up. If the lights do not immediately turn on (initial installation only) the latching relays 
opened during shipment and will close within 30 secs.  

Note: If the sensor loses power, the relays will latch to ON.  

Important Safety Information 

- Whenever it is suspected that an unsafe 
condition exists, switch off power at the 
circuit breaker and replace the device.  
Safety is likely to be impaired if, for 
example, the equipment fails to perform the 
intended functions or if the equipment 
shows visible damage.  Do not paint the 
device. 

- Use only a soft damp cloth to clean, never 
use any abrasive or chemical cleaner. 

Product Description 

Function Definitions 

2 Occupancy Time Delay 

The length of time an occupancy sensor will 
keep the lights on and at full bright after it last 
detects occupancy (assuming minimum on 
time has been met) 

3 Dim to Off Time 

An extended length of time after the 
occupancy time delay has expired that a 
sensor will first reduce lighting to the low 
dimming range setting before turning 
completely off  
 

4 100 Hour Burn-In / Auto Set-Point      
  Test Mode 

Disables Minimum On Time, sets 
Occupancy Time Delay to 30 sec, and 
shortens all photocell transitions and 
dimming rates. Mode will expire after 10 
min or if function 4 is set back to Normal.

 

100 Hour Burn-In  

Overrides relay on and/or dimming output 
to full bright (typically for lamp seasoning) 

Auto Set-Point  

Photocell calibration procedure for 
detecting optimum lighting control level 

5 Ten’s Digit of Holdback Set-Point  

The ten’s digit of the target light level for 
daylight holdback in foot-candles. 

6 One’s Digit of Holdback Set-Point  

The one’s digit of the target light level for 
daylight holdback in foot-candles. 

7 Sunlight Discount Factor 

 Value used to improve the tracking accuracy 
of a photocell during periods of high daylight. 
Decreasing the value will lower the controlled 
level of the lights.

 

8 Incremental Holdback Set-Point 
Adjustment 

Alters the target light level for daylight 
holdback in foot-candles. 

10 Minimum On Time 

The length of time required for lamps to be 
on in order to prevent all short cycling that 
shortens lamp life. If occupancy time delay 
expires prior to minimum on time being 
satisfied, the lamps will remain on until time 
has been met. 
 
 
 

11 Photocell Mode 

Indicates a photocell sensor’s method of 
operation. One mode enables the sensor to 
turn the lights both on and off, while the 
other mode can only inhibit the lights from 
turning on. For dimming sensors, this mode 
enables disabling of on/off functionality. 
 

15 Dimming Range (High) 

The maximum output level (0-10 VDC) of a 
sensor with a dimming output  
 

16 Dimming Range (Low) 

The minimum output level (0-10 VDC) of a 
sensor with a dimming output  

 
 

Input Voltage: 

120-277 VAC 

Operational Frequencies: 

50/60Hz  

Load Rating: 

800W @ 120VAC; 1200W @ 277VAC; 
Motor: 1/4 HP Load; No minimum load; 
Dimming load—sinks < 20mA (~40 ballasts 
@ 0.5mA each) 

Environmental Conditions: 

Operating Temp: 14 to 160°F (-10 to 71°C) 

Storage Temp: -14 to 160°F (-26 to 71°C)  

20% to 90% non-condensing, relative 
humidity. For indoor use only.  

Size: 

Diameter: 4.55” (11.56cm);               
Depth: 1.55” (3.94cm) 

Weight: 

6oz (0.17kg) 

Regulatory compliance: 

UL, cUL, and Title 24. 

 

*Subject to change without notice. 

Specifications* 

SIDE VIEW 

TOP VIEW 

LRM2376 Wiring 

Note 

For information on additional advanced 
settings, including resetting unit to factory 
defaults, contact: 

Technical Support: 1.800.372.3331 

Automatic Dimming Control 

The LRM2376 photocell maintains the total room light level by controlling levels of 
0-10VDC dimmable ballasts.  The photocell has full On/Off control of the load 
during periods of occupancy. There is also a second occupancy time-out period 
that enables the lights to go to a dim setting before turning off. 

 

Compatible with Philips Advance Mark 7 
and EssentiaLine 0-10V series of dimmable 
electronic ballasts. 

Philips Advance Mark 7 Series 

Philips EssentiaLine Series 

Compatibility 