Philips OccuSwitch Classic LRL2390 Installation And Programming Manual Download Page 1

The Philips OccuSwitch Classic On/Off/
Automatic Dimming Photocell Sensor 
combines the On/Off Photocell Sensor with 
Automatic Dimming Control to provide the 
industry’s most intelligent control of lighting 
for daylight harvesting applications. Ideal for 
public spaces with windows like vestibules, 
corridors, or bathrooms; the sensor works 
by monitoring daylight conditions in a room, 
then controlling the lighting so as to insure 
that adequate lighting levels are maintained. 
The sensor has on/off lighting control; it 
turns off the lights when sufficient daylight is 
present and turns them on when additional 
lighting is necessary. This sensor is ceiling 
mounted, line powered and can switch 
loads directly without the need for a power 
pack. 

Mounting 

Wiring 

Turn OFF breaker of all circuits involved. Wiring the 
device with power ON could result in serious injury 
or death. 

Danger 

Parts of the sensor carry line power, which 
is a potential lethal voltage. This product 
was designed and manufactured to ensure 
maximum safety during operation and 
service.  Always read these safety 
instructions before installing, maintaining or 
servicing the product, and strictly comply 
with these instructions. 

- This product should be installed by a 
qualified electrician. 

- This device is designed for indoor use 
only.  

- Disconnect power at circuit breaker or 
fuse when servicing, installing or removing. 

- Only use with copper or copper clad wire. 

- Wire sensor to the line power according 
to the wiring scheme in this guide.  

- To avoid short circuits, do not expose this 
product to rain or condensing moisture.  
Short circuit may cause fire or electric 
shock hazard.  Operate the devices 
between 14°F to 160°F (-10°C to 71°C) 
ambient temperature.  

It is the installer’s responsibility to ensure that the 
equipment being controlled is visible from every 
control location and that only suitable equipment is 
connected to these controls. Failure to do so could 
result in serious injury or death. 
 
The product is intended to control lighting loads.  Do 
NOT use to control equipment that could create 
hazardous situations, like entrapment.  For examples, 
do NOT install this product to control motorized 
gates, garage doors, industrial doors, microwave 
ovens, heating devices, etc.  

Warning 

Note 

Once installed, the sensor may take a few 
minutes to become active. Additionally, 
there is a 45 second delay before switching 
from “Off” to “On” (this delay is 55 
seconds when connected to 50 Hz).  

Important Safety Information 

- Whenever it is suspected that an unsafe 
condition exists, switch off power at the 
circuit breaker and replace the device.  
Safety is likely to be impaired if, for 
example, the equipment fails to perform the 
intended functions or if the equipment 
shows visible damage.  Do not paint the 
device. 

- Use only a soft damp cloth to clean, never 
use any abrasive or chemical cleaner. 

Product Description 

Function Definitions 

 

4 100 Hour Burn-In / Auto Set-

Point      

100 Hour Burn-In  

Overrides relay on and/or dimming 

output to full bright (typically for 

lamp seasoning) 

Auto Set-Point  

Photocell calibration procedure for 

detecting optimum lighting control 

level 

5 Ten’s Digit of Holdback Set-

Point  

The ten’s digit of the target light level 

for daylight holdback in foot-candles. 

6 One’s Digit of Holdback Set-

Point  

The one’s digit of the target light level 

for daylight holdback in foot-candles. 

 

 

7 Sunlight Discount Factor 

 Value used to improve the tracking 

accuracy of a photocell during periods 

of high daylight. Decreasing the value 

will lower the controlled level of the 

lights.

 

8 Incremental Holdback Set-Point 

Adjustment 

Alters the target light level for daylight 

holdback in foot-candles. 

15 Dimming Range (High) 

The maximum output level (0-10 VDC) 

of a sensor with a dimming output  

16 Dimming Range (Low) 

The minimum output level (0-10 VDC) 

of a sensor with a dimming output  

 

 

Input Voltage: 

120-277 VAC 

Operational Frequencies: 

50/60Hz  

Load Rating: 

800W @ 120VAC; 1200W @ 277VAC; 
Motor: 1/4 HP Load; No minimum load; 
Dimming load—sinks < 20mA (~40 ballasts 
@ 0.5mA each) 

Environmental Conditions: 

Operating Temp: 14 to 160°F (-10 to 71°C) 

Storage Temp: -14 to 160°F (-26 to 71°C)  

20% to 90% non-condensing, relative 
humidity. For indoor use only.  

Size: 

Diameter: 4.55” (11.56cm);               
Depth: 1.55” (3.94cm) 

Weight: 

5oz (0.14kg) 

Regulatory compliance: 

UL, cUL, and Title 24. 

 

*Subject to change without notice. 

Specifications* 

LRL2390 Wiring 

The sensor enclosure accommodates 
mounting to a variety of junction boxes 
ranging in size from a single gang mud ring 
at a 3.28” spacing, up to a round fixture box 
spacing of 3.5”. 

Daylight Harvesting 

Note 

For information on additional advanced 
settings, including resetting unit to factory 
defaults, contact: 

Technical Support: 1.800.372.3331 

 

As daylight increases and decreases throughout the day, the Automatic Dimming Control feature adjusts the  
0-10V output to vary the level of the connected loads. When sufficient daylight is present to maintain a level 
of light equal to or above the set-point level, the sensor will switch off the ballast completely. 

OccuSwitch Classic 

LRL2390 

 

 

 

Installation and 

Programming Guide 

(-) 

(+) 

Compatible with Philips Advance Mark 7 
and EssentiaLine 0-10V series of dimmable 
electronic ballasts. 

Philips Advance Mark 7 Series 

Philips EssentiaLine Series 

Compatibility 