background image

Sensors

EasySense

Fixture-Mount 

Philips EasySense 

Quick Installation Guide

Commercial Product Name

Order Code

EasySense Fixture-Mount Sensor

SNS100
SNS102
SNS200

Connection 

Color

White

Neutral

Black

Line

Green

Ground

Purple

SR+

Brown

SR-

Compatible LED Drivers

Sensor Part Number

Driver Model Number

Description

XI040C110V054VPT1

Xitanium 40W 0.1-1.1A 27-54V 120-277V SR

XI075C200V054VPT1

Xitanium 75W 0.1-2.0A 27-54V 120-277V SR

Specifications available at www.philips.com/XitaniumSR.  

Wiring Diagram

XITANIUM SR 

LED DRIVER

EASYSENSE

LED+

LED+

LED-

LED-

RSET2
SGND

NFC ANTENNA

SR-

Connectors 

SR+

SR
SR

LINE
NEUTRAL

GROUND

NC

Connectors
(non-polarized) 

Use 18AWG solid copper wire, 
rated >=600V/90C.  
Strip wire to 3/8”.

Electrical Information

Input Voltage

Powered by SR driver low-voltage interface

Current Consumption 

13mA

Nominal Power Consumption

200mW

Standby Power

< 1 W on luminaire level, including driver standby power

Occupancy Sensing

Type

Passive infrared (PIR)

Enable/Disable

Default enabled

Detection

Off/Auto-on; Red LED indicates “on”

Eco On Level  

0-100%

Hold Time

0.5-60 minutes

Viewing Angle

X=72°, Y = 86° ( See detection pattern)

Background Light Level

0-100%

Prolong Time

0 minutes - infinity

Grace Fading

0-25 sec

Response Time/Fading to Switch On/Off 

0.7Sec

Daylight Sensing

Enable/Disable

Default enabled

Auto-calibration

Upon power-up

Viewing Angle

40° (half value sensitivity); 2% cut-off point at 75°

Task Tuning
Full Light Setting

0-100%

Environment & Approbation

Operating Ambient Temperature Range

0°C to 55°C

Operating Humidity

0–95% non condensing

Storage Temperature

-25°C to 85°C

Storage Humidity

0-95% non condensing

Max Case Temperature (Tcase)

55°C

Agency Approbations

UL, CSA; Tested and approved for use in plenums; FCC ID:  
2AF2N-SNS100; IC: 20659-SNS100

Certification

California Title 20

Limited Warranty

5 years

Digital Interface

Xitanium SR

Other

Status Indicators

Red, Yellow. Yellow LED on: Vacancy & Sensor is functional;  
Red LED on: Motion is detected

No. Drivers per Sensor

Four (max)

Field Configuration

via NFC or IR.  Parameters set via Philips field apps

© 2016 Philips Lighting Holding B.V. All rights reserved.  
Philips reserves the right to make changes in specifications  
and/or to discontinue any product at any time without notice  
or obligation and will not be liable for any consequences  
resulting from the use of this publication.
philips.com/easysense

Philips Lighting North America Corporation
10275 W. Higgins Road, Rosemont IL 60018
Tel: 800-322-2086  Fax: 888-423-1882
Customer/Technical Service: 800-372-3331
OEM Support: 866-915-5886

Philips Lighting Canada Ltd.
281 Hillmount Rd, Markham, ON, Canada L6C 2S3
Tel. 800-668-9008

PLt-15142QG_EasySense QIG_060612  06/16  page 1 of 2
Document #: 4435 631 00371 REV. B

Operation and Configuration via Mobile App 

EasySense operates immediately upon installation and energization without further commissioning. If changes from  
default settings are desired, EasySense can be configured via Philips field apps through NFC or IR. For a complete  
description of the features and default settings—as well as details on the app—refer to www.philips.com/easysense. 

FCC and IC Statement 

This device complies with part 15 of the FCC rules for the United States and Industry Canada (IC) license-exempt RSS  
standard(s). Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and 
(2) this device must accept any interference received, including interference that may cause undesired operation. Any 
changes or modifications not expressly approved by Philips could void the user’s authority to operate this equipment.  
This product is intended for commercial use only.

Déclaration De Conformité À La Fcc/Ic 

Ce dispositif est conforme à la partie 15 des règles de la Federal Communications Commission (FCC) des États-Unis et 
d’Industrie Canada (IC) exempts de licence RSS norme(s). Son fonctionnement est assujetti aux deux conditions suivantes 
: (1) Ce dispositif ne doit pas provoquer de brouillage préjudiciable, et (2) il doit accepter tout brouillage reçu, y compris 
le brouillage pouvant entraîner un mauvais fonctionnement. Tous les changements ou modifications non expressément 
approuvés par Philips, sont susceptibles d’annuler le droit de l’utilisateur à se servir de cet équipement. Ce produit est 
exclusivement destiné à un usage commercial.

Connection 

Color

Red

LED+

Blue

LED-

Orange

RSET2

Green

SGND

Reviews: