List of Configuration Parameters
Field Task Level
Field task Level can be tuned to reduce the maximum output of a luminaire
to a certain percentage of the AOC (adjustable output current) of the SR
driver. After installation, there is a possibility that the field task light level is
not set according to the end user needs (e.g. light level too high). Task light
level is a configurable parameter and can be adjusted by the installer or
building maintenance personnel to a value between 1% and 100% through
the app.
Eco-on Level
A configurable light level to enable eco-friendly light behavior, enabling
energy savings. In automatic behavior, lights switch on to Eco-on Level and
it can be set to a value between Field Task level and Background Light
Level. With a manual switch override, a user could dim up from Eco-on level
to Task Level.
Background Light Level
A configurable light level that can be set as the lowest dim level and enables
comfort for end users. This light level comes into play when the hold time
has expired and before the lights switch off completely after a prolonged-
period.
Zone occupancy sharing
A configurable parameter to determine the level of occupancy sharing. If
Enabled, the occupancy sharing is over the Zone only. If disabled, the
occupancy sharing is over the entire Group.
Occupancy based Control
When enabled, occupancy detection takes place to control the lighting.
Unless commissioned into the group, the sensor does not respond to
occupancy detection. Out of the box, lights remain switched on in
nonoccupied
areas.
Occupancy mode
This feature can be configured to maximize lighting control behavior with
wireless switches. The mode options are auto on/off, manual on/off and
manual on/auto off. For more details, refer Page 27.
Group/Zone occupancy sharing
It is a configurable feature which enables EasySense SNS210 MC to share its
local occupancy detection status with the rest of the group. This can enable
granular dimming i.e. when presence is detected within the group, the
luminaires in non-occupied areas or ‘elsewhere’ can be configured to stay
at a desired light level (specified by Group light behavior parameter).
In case occupancy based control is disabled while group occupancy sharing
being enabled, elsewhere occupancy is taken as local occupancy trigger.
Group light behavior
It enables choice of light behavior for the rest of the group i.e. to determine
the light levels of lights within a group that reside in non-occupied areas.
Group light behavior enables granular dimming of lights within a group and
brings comfort to users via lighting.
EasySenseSNS210 MC sensor can be configured using the MasterConnect App. The following parameters can be configured via MasterConnect App for entire
group of lights or a single light.
Summary of Contents for EasySense SNS210 MC
Page 1: ...April 2022 Sensors EasySense SNS210 MC Installer End User Manual ...
Page 7: ...7 Commissioning ...
Page 25: ...25 Maintenance ...
Page 36: ...36 Configuration ...