NORMAL OPERATION/MANUAL TEST

 

OP-PANEL INDICATORS/OPERATION:

 

 

 

GREEN - Status:   Solid indicates system normal and AC power is on. 

NOTE:  To start the Manual test, simply press the Green Indicator (button) as indicated below. To Reset/Cancel a test press the Green Indicator 

(button) once during any test. When Unit is in test mode the Green Indicator LED is flashing.

 

 

 

1 Press:   perform a 5-sec brief lamp test, all Lamps operating from battery only.  

 

2 Presses:   perform a 1-min diagnostic test, all Lamps operating from battery only.  

 

3 Presses:   perform a 90-min diagnostic test, all Lamps operating from battery only.  

 

6-sec Continuous Press:  perform a RESET operation.

 

 

CONTINUOUS MONITORING:  The system monitors the following continuously:  
Battery, 2) Lamps, 3) Charger, 4) Transfer function.

 

 

 

The battery requires at least 72 hours of charge time to perform any extended diagnostic test. If the battery has not charged for 72 hours after 

installation and a diagnostic test is requested, the charger light will come on and stay on for one minute indicating that the battery is not fully charged 

for attempted test. (The 5-sec brief lamp test is always allowed.)

 

 

Emergency Lighting

 

COMPAC  Thermoplastic Unit Equipment

 

 
 
 

 
 
 

 
 
 

 
 

 

 

No Rigid Conduit 

  

Flexible Conduit Only

 

CAX/CTX Series 

INSTRUCTION SHEET 

 

OPTIONAL FACTORY EQUIPPED ITEMS:

 

 

REMOTE: Unit will be supplied with pigtail connector cable required to control and operate a remote of up to rated MAX. wattage.

 

 

 

TIME DELAY (TD): After a power failure and power is restored, the lamps will remain lit for a 15-min period (provided battery capacity remains).

 

 

Note: The Green power indicator LED will flash slowly during the 15-min. period.

 

 

 

LASER TEST (LX): To operate using a laser pen: use laser pen and point the laser beam over the remote sensor (see below), thereby duplicating 

the manual button (1,2,3) pushes. The laser must impact the remote sensor for at least 0.2 seconds to be recognized.

 

 

 

LESS SELF-TEST (LS): Monthly automatic self-tests will not be performed. (Lamps will not energize on an automatic monthly schedule.)

 

 

TROUBLE  INDICATORS/TROUBLESHOOTING

 

IMPORTANT SAFEGUARDS

 

READ AND FOLLOW ALL  SAFETY INSTRUCTIONS

 

 

WARNING: Electrical Shock Potential!! Do not attempt to install, maintain or relamp without disconnecting 
all power. Failure to disconnect power can result in electrocution, shock, or severe burns.

 

 

CAUTION: This fixture is designed for permanent installation in ordinary (NON-HAZARDOUS) locations in 
accordance with the National Electrical Code and all applicable local codes. Do not use in areas of limited 
ventilation or in high ambient enclosures. The lamp and fixture operate at high temperatures; contact with 
combustible material can cause fire and personal contact can cause severe burns. When using electrical

 

 

TEST 

Button

 

 
 
 
 
 
 
 
 
 

 

REMOTE SENSOR

 

(IF EQUIPPED)

 

Xtest  DISPLAY  PANEL  INDICATOR:

 

 

 

GREEN - Status:  solid indicates system normal and AC power is on and flashes during any 
manual/auto test cycle.

 

 

RED – CHARGER FLASHING:  a charger failure requires the diagnostic charger board to be 
replaced.  

 

RED – BATTERY FLASHING:  battery is disconnected or if it is connected, a replacement is 
needed. RED - LAMP FLASHING:  Lamp(s) is disconnected or if it is connected, a replacement is 

needed. (If 
4-pin remote pigtail is connected to diagnostic charger board and no remote lamp is attached, the 
LAMPS indicator will flash. Connect a remote lamp or disconnect remote pigtail.)

 

 

ALL 3 RED FLASHING:  bad transfer; battery and lamps are disconnected or if they are 
connected a replacement diagnostic charger board is needed.

 

equipment, basic safety precautions should always be followed; including the following:

 

 

READ AND FOLLOW ALL SAFETY INSTRUCTIONS.

 

 

Do not use outdoors.

 

 

Do not let power supply cords touch hot surfaces.

 

 

Do not mount near gas or electric heaters.

 

 

Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If 
acid is spilled on skin or in eyes, flush acid with fresh water and contact a physician 
immediately.

 

 

Equipment should be mounted in locations and at heights where it will not readily be

 

WIRING 

INFORMATION

 

 
 

 

Transformer Inputs

 

 
BLACK - 120V

 

WHITE - Common or Neutral

 

RED - 277V

 

 

 

Battery Connector

 

 

 
 
 
 
 
 
 
 

Transformer Connector

 

 

 

Remote Connector

 

(Optional)

 

 
 
 
 
 
 
 
 
 

Lamp 

Connectors

 

subjected to tampering by unauthorized personnel.

 

 

The use of accessory equipment not recommended by the manufacturer may cause an 
unsafe condition.

 

 

CAUTION: Halogen cycle lamp(s) are used in this equipment. To avoid shattering: Do not 
operate lamp in excess of rated voltage, protect lamp against abrasion and scratches and 
against liquids when lamp is operating, dispose of lamp with care.

 

 

Halogen cycle lamps operate at high temperatures. Do not store or place flammable 
materials near lamp.

 

 

Do not use this equipment for other than intended use.

 

 

Servicing of this equipment should be performed by qualified personnel only.

 

                   

 

 

SAVE THESE  INSTRUCTIONS

 