background image

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

! IMPORTANT SAFEGUARDS !

WHEN USING ELECTRICAL EQUIPMENT, BASIC

SAFETY PRECAUTIONS SHOULD ALWAYS BE 

FOLLOWED, INCLUDING THE FOLLOWING:

SAVE THESE INSTRUCTIONS

THIS PRODUCT CONTAINS A RECHARGEABLE NICKEL-CADMIUM BATTERY.  

THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.

© Philips Emergency Lighting

A Division of Philips Electronics North America Corporation 

236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-854-1630 • www.philips.com/bodine

75020054

FLUORESCENT EMERGENCY BALLAST

Installation Instructions

  1.  To prevent high voltage from being present on red & yellow output leads prior to installation, inverter  
    connector must be open. Do not join inverter connector until installation is complete and AC power is  
    supplied to the emergency ballast.
  2.  This product is for use with one 17 W through 215 W  (2’ - 8’) or two 17 W through 40 W (2’ - 4’) single  
    pin or bipin fluorescent lamps, including standard, energy saving, HO, VHO, circline, U-shaped and 
    rapid-start (4-pin) long compact fluorescent lamps.
  3.  Make sure all connections are in accordance with the National Electrical Code and any local regulations.
  4.  To reduce the risk of electric shock, disconnect both normal and emergency power supplies and inverter  
    connector of the emergency ballast before servicing.
  5.  This emergency ballast is for factory or field installation in either the ballast channel or on top of the  
    fixture.
  6.  This product is suitable for damp locations where the ambient temperature for fixture is 0°C minimum,  
    +50°C maximum. Product is also suitable for installation in sealed and gasketed fixtures. Product is not  
    suitable for heated air outlets and wet or hazardous locations.
  7.  An unswitched AC power source is required (120 or 277 VAC, 60 Hz).
  8.  Do not install near gas or electric heaters.
  9.  Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field
    replaceable. Contact the manufacturer for information on service.
 10.  The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
 11.  Do not use this product for other than intended use.
 12.  Servicing should be performed by qualified service personnel.

B50LP

Ni - Cd

09/21/09

Summary of Contents for B50LP

Page 1: ...d start 4 pin long compact fluorescent lamps 3 Make sure all connections are in accordance with the National Electrical Code and any local regulations 4 To reduce the risk of electric shock disconnect both normal and emergency power supplies and inverter connector of the emergency ballast before servicing 5 This emergency ballast is for factory or field installation in either the ballast channel o...

Page 2: ... on top of fixture 2 UNSWITCHED FIXTURE SWITCHED FIXTURE E M E R G E N C Y A C B A L L A S T B A L L A S T BLACK WHITE WHITE WHT BLK COMMON E M E R G E N C Y A C B A L L A S T B A L L A S T BLACK WHITE WHITE WHT BLK COMMON E M E R G E N C Y A C B A L L A S T B A L L A S T BLACK WHITE WHITE WHT BLK COM WALL SWITCH WHT RED B L K B L K CAP UNUSED LEAD BLACK 120V OR ORANGE 277V HOT E M E R G E N C Y A...

Page 3: ...t installed in the fixture Select the appropriate wiring diagram on back to connect the emergency ballast to the AC ballast and lamp s Make sure all connec tions are in accordance with the National Electrical Code and any local regulations After installation is complete supply AC power to the emergency ballast and join the inverter connector At this point power should be connected to both the AC b...

Page 4: ...G Refer to Table 1 before connecting E M E R G E N C Y B A L L A S T BLACK WHITE WHITE WHT BLK COMMON WALL SWITCH WHT RED RED WHITE VIOLET BROWN CAP UNUSED LEAD BLACK 120V OR ORANGE 277V INVERTER CONNECTOR HOT ITS BLACK BLK BROWN VIOLET EMERGENCY LAMP 1 LAMP 2 LAMP 3 LAMP 4 4 LAMP INSTANT START BALLAST WARNING Refer to Table 1 before connecting BLUE BROWN BROWN RED YELLOW YEL BLK BLU WHT BLUE BLUE...

Page 5: ... BLK BLU WHT BLUE RED RED YELLOW YELLOW LAMP 1 LAMP 2 WARNING Do NOT connect brown connector FIG CP129 FOUR 4 LAMP INSTANT START BALLAST FIG CP128 FOUR 4 LAMP RAPID START BALLAST E M E R G E N C Y B A L L A S T BLACK WHITE WHITE WHT BLK COMMON WALL SWITCH WHT RED RED WHITE VIOLET BROWN CAP UNUSED LEAD BLACK 120V OR ORANGE 277V INVERTER CONNECTOR HOT ITS BLACK BLK BROWN VIOLET LAMP 1 LAMP 2 LAMP 3 ...