SPRH870 SERIES

Emergency Downlighter Surface Ceiling

Class 

1

IP

20

FEATURES

   

Model

Downlighter 
features

Supply voltage

Maximum luminaires on a 
Type B, 10A circuit breaker

Part No.

Non-Maintained

NM3

220-240V AC 50/60 Hz

90 Luminaires

SPRH870LN

Self Test

NM3 AutoTest

220-240V AC 50/60 Hz

90 Luminaires

SPRH870YS

DALI

NM3 DALI

220-240V AC 50/60 Hz

90 Luminaires

SPRH870DS

Central Supply

220-240V AC 50/60 Hz
176-264V DC

30 Luminaires

SPRH870LA

Central Supply
DALI

DALI

220-240V AC 50/60 Hz
176 - 280V DC

30 Luminaires

SPRH870DA

IMPORTANT-SAFETY

Before carrying out any servicing on this luminaire, ensure that the mains supply is fully isolated. 
Disconnect luminaire before insulation testing of the installation.

   

   

WARNING

Do not stare at operating lamp. It may be harmful to the eyes.

   

LUMINAIRE DIMENSIONS- NON-MAINTAINED, SELF TEST AND DALI

252

160

45

15

200 CENTRES

36

CENTRES

50

CENTRES

36

CENTRES

Ø20 CABLE ENTRY

8 NO. FIXING HOLES Ø5

79

Ø20 KNOCK

OUT

(THIS SIDE ONL

Y)

Summary of Contents for SPRH870 Series

Page 1: ...upply 220 240V AC 50 60 Hz 176 264V DC 30 Luminaires SPRH870LA Central Supply DALI DALI 220 240V AC 50 60 Hz 176 280V DC 30 Luminaires SPRH870DA IMPORTANT SAFETY Before carrying out any servicing on this luminaire ensure that the mains supply is fully isolated Disconnect luminaire before insulation testing of the installation WARNING Do not stare at operating lamp It may be harmful to the eyes LUM...

Page 2: ...IS MAINTAINED BETWEEN THE LV SUPPLY AND CONTROL CONDUCTORS ON THIS LUMINAIRE DALI Dimensions Connections USL N DALI DALI N L N DALI DALI NM3 AutoTest DALI USL DALI L N 160 160 47 15 35 9 12 35 53 71 148 45 62 80 98 115 Ø20 KNOCKOUT THIS SIDE ONLY Ø5 FIXING HOLES Ø20 CABLE ENTRY SPRA860DS SPRC860DS SPRE860DS 220 240V AC 50 60 Hz DALI NM3 90 luminaires Do not stare at operating lamp It may be harmfu...

Page 3: ...GENERAL INSTALLATION METHOD NON MAINTAINED SELF TEST AND DALI 2 1 GENERAL INSTALLATION METHOD CENTRAL SUPPLY AND CENTRAL SUPPLY DALI 1 REAR CABLE ENTRY SURFACE CABLE ENTRY OPTION SURFACE CABLE ENTRY OPTION REAR CABLE ENTRY ...

Page 4: ... connected correctly to the luminaire prior to applying power Do not interrupt unswitched supply during self commissioning period Please allow 51 hours for charge discharge charge cycle FAULT RECTIFICATION SEQUENCE 1 Fault Identification Slow Red Flash Battery Fault Permanent Red Lamp Fault Charge Fault 2 Take Remedial Action Check Lamp Replace Lamp Check Battery Replace Battery Check Module Repla...

Page 5: ...nal PASSED 10 Funtional FAILED REPLACED BATTERY 11 Funtional PASSED 12 3 Hour Duration PASSED Each month or more frequently if a fault is identi fied we recommend the installation is checked for status of L E D s Corrective action if necessary should be taken and recorded on the above form Follow good practice as laid down in relevant legislation such as BS 5266 TO RESET AFTER A FAULT SWITCH LUMIN...

Page 6: ...me case for example water ingress to electronic circuits may cause a fire Please contact our Technical Department for advice Modifications Philip Payne products should not be modified Any modification may render the product unsafe and will invalidate any Safety Approval marks Philip Payne will not accept any responsibility for any modified products or for any damage caused as a result of their mod...