Pfannenberg DTS 8000E Operating And Assembly Instruction Manual Download Page 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

     

外挂式机柜空调操作及使用说明书

 

     DTS 8000E 50/60Hz

系列

 

     Operating and assembly instruction 

     For side-mounted cooling units 

     DTS 8000E 50/60Hz 

Summary of Contents for DTS 8000E

Page 1: ...外挂式机柜空调操作及使用说明书 DTS 8000E 50 60Hz 系列 Operating and assembly instruction For side mounted cooling units DTS 8000E 50 60Hz ...

Page 2: ... 2 储运 7 2 3 开箱 7 3 供货范围 8 4 一般信息 8 5 铭牌 8 6 安全 9 7 功能 9 7 1 配置与功能 9 7 2 工作原理 9 7 3 冷凝物 10 8 技术规格书 11 8 1 电气原理图 11 8 2 备品备件 13 8 3 安装开孔 14 8 4 气流原理 17 8 5 技术参数 18 9 安装 25 9 1 概述 25 9 2 安装工作 25 9 3 电气连接 26 10 运行条件 26 11 投入使用和功能 27 ...

Page 3: ...0 14 停止使用 30 15 故障排除 30 16 保障条款 30 附表 I 31 1 Hints on the manual 32 2 Handling 32 2 1 Transport 32 2 2 Storage 32 2 3 Unpacking 33 3 Scope of delivery and options 33 4 General Information 33 5 Name plate 33 6 Safety 34 7 Function 34 7 1 Function and configuration 34 7 2 Operating principles 35 7 3 Condensate 35 ...

Page 4: ...nnection 51 10 Operating condition 52 11 Putting into operation and function 52 11 1 General remarks 52 11 2 Operation display 52 11 3 Start up Test mode 53 11 4 Door contact 53 11 5 Equipment fault 53 12 Parameters View and Settings 54 13 Cleaning and Maintenance 55 13 1 Cleaning 55 13 2 Maintenance 55 14 When not in used 55 15 Trouble shooting 56 16 Warranty Conditions 56 Appendix I 57 ...

Page 5: ...格遵守所述的措施 将有可能造成生命财物损失 提示包含关于所述措施或指导的额外信息 2 搬运 2 1 运输 只能通过壳体或吊环来提升机柜空调 M8吊环不在供货范围 运输时保持机柜空调处于最终使用时相同的摆放状态 如果整体机柜需要运输 请在运输前将机柜空调拆下并单独包装 不按照这些指导操作 将导致保障条款失效 2 2 储运 储存环境不应超过70 储存时使机组处于最终使用时的摆放状态 不按照这些指导操作 将导致保障条款失效 2 3 开箱 开箱过程中应当仔细查看机柜空调 看是否存在因运输造成的破坏 尤其注意是否有部件松动 凹坑 擦伤和 漏油等 任何损坏应当立即通知承运商 见保障条款 并且适用 百能堡产品售后服务声明 的最新版本 请在安装机组前完整仔细阅读此手册 本手册构成标准产品不可分割的一部 分 必须保存至机组报废为止 ...

Page 6: ...安装时务必带保护手套 要求保障时 需要提供故障的确切信息 如有可能请提供照片 机种型号和序列号 3 供货范围 供货范围包括 机柜空调 附件包 包括紧固件 插头式电气连接器等 特殊的附件 如适用 4 一般信息 百能堡可以妥善处理旧设备 但客户需承担运输费用 百能堡生产的机柜空调不含以下物质 多氯三联苯 石棉 甲醛 镉 液态有害物质 对每台机柜空调进行检查以确保它是完全依照9 ProdSV的规定 德国事故预防法规 交货前百能堡已对每台空调在工厂进行电气安全检测 5 铭牌 安装和维护 请注意机器背部铭牌标注的详细技术信息 ...

Page 7: ... 7 1 配置与功能 1 15 55 外部环境温度 2 内部控制温度 25 45 3 冷凝水蒸发器 可选 4 IP54 IP34防护 5 2 400V交流供电 可选 机柜冷却器有5度回差 即当内部设定温度为35 设备将在内部温度30 以下时停止制冷 机柜空调的具体功能见技术规格书 见章节8 7 2 工作原理 压缩机 1 将制冷剂压缩到高压 在这个过程中温度升高 冷凝器 2 中 热量散失到周围环境空气 中 制冷剂变成液体 冷凝器风扇 5 吸入并使空气通过冷凝器 然后排放出去 在截流装置 3 中 冷却液的压力下降 在蒸发器 4 中 冷却剂吸收机柜内空气中的热量并蒸发 因此 来自机柜中 的空气被冷却下来 同时机柜内的空气被除湿 蒸发器风 6 吸出机柜内的空气并迫使其通过蒸发器 冷却空气吹回到机柜内 机柜空调是由电子系统控制的 温度传感器 7 记录了机柜内的空气温度 所 使用制冷剂不损害臭氧层 而...

Page 8: ...水分被凝聚成冷凝水 为了避免对电控柜及本制冷系统发生任 何损害 必须排出冷凝水 冷凝水排放方式如下 带冷凝水蒸发器 可选 的制冷设备在正常情况下 可以蒸发掉水分 但为防止蒸发器故障后产生的 冷凝水溢流 请连接冷凝水管路 然后再通过水管排出 始终确保冷凝水正确地排出 在特定情况下有可 能会发生凝结水过量 例如 机柜不密封或机柜内部温度经常低于露点温度 在正常运行过程中发生冷凝水过量 请检查机柜的密封 我们建议安装一个门接触开关 当机柜门被打开时 机柜空调将自动关闭 以防止过度冷凝水 ...

Page 9: ...685408021C 11 8 技术规格书 8 1 电气原理图 230 400V 2 电气原理图 电 冷凝器风扇 电 蒸发器风扇 压缩机 电 压缩机 温度 头 冷凝水蒸发器 2 1 F2 C11 C12 C13 E1 F F1 5 54 M1 M3 M2 TS1 4 42 1 2 ...

Page 10: ...685408021C 12 400V 3 电气原理图 电 冷凝器风扇 5 54 M1 2 1 F2 M3 M2 C11 C12 电 蒸发器风扇 压缩机 C13 电 压缩机 E1 TS1 温度 头 4 42 冷凝水蒸发器 1 2 3 4 5 T1 变压器 1 电器 2 F1 ...

Page 11: ... 18864000002 18864000002 压缩机电 18864000009 18864000009 18864000011 18864000011 过滤干燥器 18865000002 18865000002 18865000002 18865000002 控制器 物料号位于控制器上 备用件 DTS 8441E DTS 8541E DTS 8841E 230V DTS 8841E 400V 内风机 18861100020 18861100022 18861100022 18861100022 外风机 18861100021 18861100022 18861100022 18861100022 盖板 RAL7035 18860200016 18860200033 盖板 VAH 18860200020 18860200034 压缩机 18861200004 18861200014 内风...

Page 12: ...685408021C 14 8 3 安装开孔 DTS 8021E 密封泡棉粘贴效果图 开孔尺寸 DTS 8031E 密封泡棉粘贴效果图 开孔尺寸 ...

Page 13: ...685408021C 15 DTS 8241E DTS 8341E DTS 8441E DTS 8541E 密封泡棉粘贴效果图 开孔尺寸 ...

Page 14: ...685408021C 16 DTS 8841E 密封泡棉粘贴效果图 开孔尺寸 ...

Page 15: ...685408021C 17 8 4 气流原理 在安装此设备前应当完整仔细地阅读此说明 此说明是设备不可分割的一部分 在设备报废请前务必保留 安装前 请确认设备间以及设备至墙体的距离至少有 200 毫米的间距 在柜子内部的进风口以及出风口没有 干涉以及障碍 ...

Page 16: ... F 45 C 113 F 外循环气流量 282 336 m h 内循环气流量 224 257 m h 冷凝水排放 冷凝水管 噪音 1m 62 dB A 电气数据 电源频率 50 60 Hz 工作范围 DIN IEC 60038 额定电压 230 V 电力消耗 P el 285 305 W 电流 I nom max 1 7 A 启动电流 I Start max 3 0 A 尺寸 高 X 宽 X 深 400 X 282 X 160 mm 重量 11 5kg 安装状态 垂直 结构 标准 钢板 可选 不锈钢 防腐处理 标准 镀锌 静电喷粉 可选 不锈钢 铝 防护等级 IP 54 对机柜 EN 60529 正确安装操作为前提 IP 34 对环境 EN 60529 正确安装操作为前提 需安装前外壳 铭牌信息 无过滤网 可选 情况下制冷量 自由送风 空调电器接口处另需电器端子空间40mm ...

Page 17: ...据 电源频率 50 60 Hz 工作范围 DIN IEC 60038 额定电压 230 V 400 V 2 电力消耗 A35 A35 P el 289 332 W 358 396 W 电流 I nom max 1 7 1 73 A 1 58 1 6 A 启动电流 I Start max 3 5 A 3 5 A 冷凝水蒸发器 CM P el 可选 30 110W A35 A35 ca 70W 尺寸 DTS 8031E 230V DTS 8031E 400V 高 X 宽 X 深 670 X 325 X 200 mm 重量 17 3 kg 25 3 kg 冷凝水蒸发器重量 可选 0 5kg 安装状态 垂直 结构 标准 钢板 可选 不锈钢 防腐处理 标准 镀锌 静电喷粉 200 C 可选 不锈钢 铝 防护等级 IP 54 对机柜 EN 60529 正确安装操作为前提 IP 34 对环境 EN 60...

Page 18: ...数据 电源频率 50 60 Hz 工作范围 DIN IEC 60038 额定电压 230 V 400 V 2 电力消耗 A35 A35 P el 513 587 W 589 662 W 电流 I nom max 3 1 3 37 A 2 25 2 33A 启动电流 I Start max 10 5 A 8 25A 冷凝水蒸发器 CM P el 可选 30 110W A35 A35 ca 70W 尺寸 DTS 8241E 230V DTS 8241E 400V 高 X 宽 X 深 1350 X 400 X 200 mm 重量 33 5 kg 41 2 kg 冷凝水蒸发器重量 可选 0 5kg 安装状态 垂直 结构 标准 钢板 可选 不锈钢 防腐处理 标准 镀锌 静电喷粉 200 C 可选 不锈钢 铝 防护等级 IP 54 对机柜 EN 60529 正确安装操作为前提 IP 34 对环境 EN...

Page 19: ...50 60 Hz 工作范围 DIN IEC 60038 额定电压 230 V 400 V 2 电力消耗 A35 A35 P el 596 678 W 632 709 W 电流 I nom max 3 48 3 49 A 2 45 2 49 A 启动电流 I Start max 11 A 8 7 A 冷凝水蒸发器 CM P el 可选 30 110W A35 A35 ca 70W 尺寸 DTS 8341E 230V DTS 8341E 400V 高 X 宽 X 深 1350 X 400 X 200 mm 重量 34 1 kg 41 8 kg 冷凝水蒸发器重量 可选 0 5kg 安装状态 垂直 结构 标准 钢板 可选 不锈钢 防腐处理 标准 镀锌 静电喷粉 200 C 可选 不锈钢 铝 防护等级 IP 54 对机柜 EN 60529 正确安装操作为前提 IP 34 对环境 EN 60529 正...

Page 20: ... 电气数据 电源频率 50 60 Hz 工作范围 DIN IEC 60038 额定电压 230 V 400 V 2 电力消耗 A35 A35 P el 734 822 W 784 879 W 电流 I nom max 5 8 5 97 A 5 1 5 29 A 启动电流 I Start max 15 A 11 8 A 冷凝水蒸发器 CM P el 可选 30 110W A35 A35 ca 70W 尺寸 DTS 8441E 230V DTS 8441E 400V 高 X 宽 X 深 1350 X 400 X 230 mm 重量 43 kg 50 7 kg 冷凝水蒸发器重量 可选 0 5kg 安装状态 垂直 结构 标准 钢板 可选 不锈钢 防腐处理 标准 镀锌 静电喷粉 200 C 可选 不锈钢 铝 防护等级 IP 54 对机柜 EN 60529 正确安装操作为前提 IP 34 对环境 EN...

Page 21: ...数据 电源频率 50 60 Hz 工作范围 DIN IEC 60038 额定电压 230 V 400 V 2 电力消耗 A35 A35 P el 1068 1173 W 1089 1205 W 电流 I nom max 7 9 8 04 A 7 0 7 44 A 启动电流 I Start max 18 4 A 13 8 A 冷凝水蒸发器 CM P el 可选 30 110W A35 A35 ca 70W 尺寸 DTS 8541E 230V DTS 8541E 230V 高 X 宽 X 深 1350 X 400 X 250 mm 重量 51 6 kg 65 kg 冷凝水蒸发器重量 可选 0 5kg 安装状态 垂直 结构 标准 钢板 可选 不锈钢 防腐处理 标准 镀锌 静电喷粉 200 C 可选 不锈钢 铝 防护等级 IP 54 对机柜 EN 60529 正确安装操作为前提 IP 34 对环境...

Page 22: ...频率 AC 50 60Hz 工作范围 DIN IEC 60038 额定电压 230 V 400 V 3 电力消耗 A35 A35 P el 1850 1970 W 2000 2160 W 电力消耗 A35 A50 2130 2250 W 2390 2500 W 电流 I nom max 11 5 A 7 5 A 启动电流 I Start max 30A 冷凝水蒸发器 CM P el 可选 30 110W A35 A35 ca 70W 尺寸 DTS 8841E 230V DTS 8841E 400V 高 X 宽 X 深 1510 X 485 X 330 mm 重量 70 Kg 75 Kg 安装状态 垂直 结构 标准 钢板 可选 不锈钢 防腐处理 标准 镀锌 静电喷粉 200 可选 不锈钢 铝 防护等级 IP 54 对机柜 EN 60529 正确安装操作为前提 IP 34 对环境 EN 605...

Page 23: ...铰链能够支持机柜空调的重量或当门被打开机柜时 不会翻 倒 金属碎屑可能损坏机柜 如果在安装现场开安装孔 确保使用保护罩 以免切屑进入机柜 损坏电气元件 为方便机柜空调安装 M8的吊环可以旋入机柜空调顶部固定 方便吊装 简单 一人安装 就能实现 9 2 安装工作 机柜安装面要开好空气通风口和螺栓安装固定孔 尺寸根据开孔尺寸 1 如机柜未预留机柜空调的开口 在机柜上切出开口 尺寸见开孔尺寸 然后去除剪边毛刺 2 取出附件包内密封条 标号8 9或10 11 12 贴在门板外侧 如图 先将密封条8或11上的孔与门板圆孔同 心 后再按压在门板上 然后将密封条9或10或12外边线与8或11外边线对齐后贴在门板上 3 在机柜内侧 取出附件包内的螺栓 平垫片 弹垫 螺母及螺栓 标号3 4 5 6 7 将空调锁紧 4 将出水管通过机柜空调底板 使冷凝水能自由流下 并将水管切至所需长度 ...

Page 24: ... 5平方毫米或AWG18 AWG14 在电缆的大小选择 应参照相关法规要求 7 将机柜空调插上电源 见9 3 8 不同机器可能安装方式不同 请参考随机资料 9 3 电气连接 机柜空调应当经由断路器连接到电源 请选择合适的断路器 断开断路装置时 其触点间隙应不少于3毫 米 电源线上不可以串接温度传感器 电源线上需要串接铭牌注明的保险丝 作为线路保护 电源连接和维修 如果适用 只能由授权的经过培训的电工来进行 电源连接 电源电压和频率必须符合铭牌标示值 请认真看机器上有更多带有解释的标签 如果电压过高可能会导致器件损坏 一般空调的额定电压230V或400V 10 运行条件 电压范围为额定电压的 10 以内 电源频率为额定频率的 3Hz以内 环境温度必须低于55 使用本机时注意使热交换量适合实际的需求 只使用原装备件 ...

Page 25: ...11 2 操作显示器 机柜空调装有操作显示器 上电后操作显示器显示柜内实时温度 表明机组在正常操作模式 如果发生故 障或有报警输出时 操作显示器显示报警代码 警报灯点亮并伴随报警声 这使诊断机柜空调故障更 易 见 章节15 11 3 启动自检模式 通电前 若门触点断开 则机柜空调不启动 直到门触点闭合后 机柜空调进入自检试模式 自检模式将不 受外部环境影响 机柜空调运行启动模式持续10秒 之后是自检模式持续约105秒 自检模式时 有故障设备 续运行 直到自检模式结束 产生相应的报警代码 如有故障则需解除故障后进入正常工作模式 如无故 障 直接进入正常工作模式 模式 时间曲线 特征 指示灯 启动模式 t s 9s 操作显示器显示 内部温度 自检模式 t 1 s 19s 内风机运行 t 2 s 29s 外风机运行 内风机停止 t 3 s 54s 压缩机运行 外风机停止 t 55s 115s 内...

Page 26: ...议使用一根带护线套的双绞线电缆 无需另接外部电源 如果门触点开关未被使用 需将其短接 位置见机壳标签或电气原理图 11 5 设备故障 机柜空调故障触点X54 1 2脚为常闭触点 上电后无故障为闭合 有故障时将引起X54 1 2脚触点断开并 显示告警代码 见章节15 故障指示连接最大 量为 230V 1A 12 参数查看与设置 机柜空调可以通过操作显示器对参数进行监控或设置 机柜空调电子控制系统包括主控制系统 操作显示系统 面板上的指示灯从左到右排列的功能含义如下表 指示灯 指示灯含义 长亮 备注 上电自检 自检 启用 制冷 正在制冷 启用 制热 无 除湿 无 风机 风机运转 启用 告警 告警发生 启用 操作面板 ...

Page 27: ...再按 Select 键确认进入后 通过 键选择 t1 再按 Select 键显示具体参数值 长按 键 6S 后即可调整参数值的大小 调整到正确的数值后再次按 Select 键确认修改 然后按 Mode 键返回上层菜单或者静置 5min 自动返回 主界面 如果不需要修改 直接按 Mode 键返回上层菜单即可 只有 t1 可以设置 即机柜内设定温度 其他参数只用于排除故障参考 任何画面下 无任何按键触发 300 秒后返回主画面 参数修改成功后需要返回主界面 修改值才会生效 13 清洁和维护 在任何清洁或维护操作前 请切断空调电源 13 1 清洁 建议每个月对机柜空调进行维护 例如对冷凝回路进行清洗 将提高设备的运转效率以及可靠性 具体维 护周期视使用环境而定 特别注意以下说明 清洗外部风道 冷凝器以及外风机 用软刷或高压空气进行作业 注意不要伤到翅片 步骤如下 1 断开机柜空调电源 2 打开外...

Page 28: ...理时 需根据相关环保法规由专业人员进行处理 见章节 4 15 故障排除 尽管有精心维护 还是有可能产生故障 机柜空调的实时自检功能能够准确的自行诊断设备故障 如果机器发生故障 操作显示器显示相关报警代码 用户可根据下表中的报警代码查找 使得诊断更 易 报警列表 报警代码 描述 故障排除方法 AL01 Pb1 报警 1 检查感温头 Pb1 2 检查连接线是否损坏 3 检查接头是否插错位 AL02 机柜门打开 1 检查门开关 2 检查接线是否松动 3 检查接线是否接错 AL03 超温告警 1 查看是否 AL02 报警 此时设备停止工作 2 检查内外风机是否正常工作 3 检查压缩机是否正常工作 4 检查冷凝器是否脏堵 5 检查内部风口是否堵塞 风道是否顺畅 6 检查热负荷 非授权人员不可检修此设备 16 保障条款 以下情况保障将失效 机组的不恰当使用 不适宜的运行条件或不遵守操作指导 在腐蚀或酸...

Page 29: ... 最小值 最大值 默认值 单位 PB1 内循环回风温度 可测范围 30 60 t1 设定温度 可设定范围 25 45 35 Dor 门开关 0 代表门开关断开 1 代表门开关闭合 0 1 IFR 内风机 0 代表停止工作 1 代表正在工作 0 1 EFR 外风机 0 代表停止工作 1 代表正在工作 0 1 Con 压缩机 0 代表停止工作 1 代表正在工作 0 1 ALr 故障报警 0 代表有故障输出 1 代表无故障 设备正常工作 0 1 AL01 Pb1 报警 0 代表有故障 1 代表无故障 0 1 AL02 机柜门打开 0 代表有故障 1 代表无故障 0 1 AL03 超温告警 0 代表有故障 1 代表无故障 0 1 为内部设定温度可修改设定值 当内部温度高于设定温度 t1 上15度时设备将进行高温报警 产生高温告警后如果温度下降到设定温度 t1 上的10度内 高温告警消失 所有未提及...

Page 30: ...nal information on the action or instruction described 2 Handling 2 1 Transport Lift cooling unit only by the casing or with two eyebolt rings M8 eyebolt rings are not in scope of delivery Transport the cooling unit only in condition of usage Prior to transport remove the cooling unit and pack it separately if the complete switch cabinet is to be transported Failure to observe these instructions w...

Page 31: ... and the indication of type and serial number of the cooling unit are required 3 Scope of delivery and options The Scope of delivery includes Cooling unit Enclosed package among other things fastening material electrical plug type connectors Quick guide Special accessories if applicable 4 General Information Old devices can be properly disposed of by Pfannenberg They must be sent to one of our wor...

Page 32: ...aning or maintenance operations Only original spare parts may be used 7 Function 7 1 Function and configuration 1 General external environment temperature 15 55 2 Insternal temperature control range 25 45 3 I 54 internal I 34 external protection class 4 Condensate evaporator optional for some model not available 5 2 hases 4 ac power supply optional for some model not available The unit has a 5 hys...

Page 33: ...emperature of the air inside the switch cabinet 7 The refrigerant is not detrimental to the ozonosphere it is hardly combustible 7 3 Condensate During cooling the moisture romoved from the hot air by the evaporator is collected as condensate In order to avoid any damage to the switch cabinet and the cooling unit the condensate must be discharged The condensate is discharged in the following way In...

Page 34: ...er fan Capacitors evaporator fan Fuse Operating indicator CB Compressor Condenser fan Evaporator fan Connection mains Connection failureindication door contact Option Capacitors compressor Temperaturesensor Earthing connection Condensate evaporation Overheat protector Sub terminal high pressurestat ...

Page 35: ...ndicator CB Compressor Condenser fan Evaporator fan Connection mains Connection failure indication door contact Option C13 Capacitors compressor E1 TS1 Temperature sensor 4 42 Earthing connection Condensate evaporation 1 2 3 4 5 Sub terminal T1 Control transformer 1 eay 2 Contact 3 phase voltage monitoring relay F1 high pressurestat ...

Page 36: ...essor capacitor 18864000009 18864000009 18864000011 18864000011 Filte Dryer 18865000002 18865000002 18865000002 18865000002 Controller Part number is located on the controller Spare parts DTS 8441E DTS 8541E DTS 8841E 230V DTS 8841E 400V Internal fan 18861100020 18861100022 18861100022 18861100022 External fan 18861100021 18861100022 18861100022 18861100022 Cover RAL7035 18860200016 18860200033 Co...

Page 37: ...685408021C 39 8 3 Installation Cut out DTS 8021E Effect view of the sealing Cut out Dimension DTS 8031E Effect view of the sealing Cut out Dimension ...

Page 38: ...685408021C 40 DTS 8241E DTS 8341E DTS 8441E DTS 8541E Effect view of the sealing Cut out Dimension ...

Page 39: ...685408021C 41 DTS 8841E Effect view of the sealing Cut out Dimension ...

Page 40: ...d this manual completely and carefully before installing the unit Prior to mounting ensure that the clearance of the units to each other and to the wall is at least 200mm air inlet and outlet are not obstructed on the inside of the enclosure ...

Page 41: ...l 1m 62 dB A Electrical data Mains frequency 50 60 Hz Operating range DIN IEC 60038 ated voltage 23 Power consumption A35 A35 P el 285 305 W Current consumption I nom max 1 7 A Starting current I Start max 3 0 A Dimensions eight Width Depth 4 282 16 mm Weight 11 5kg Installation position vertical Unit construction Standard steel Option Stainless Corrosion protection Standard galvanized electrostat...

Page 42: ... 38 ated voltage 23 4 2 Power consumption A35 A35 P el 289 332 W 358 396 W Current consumption I nom max 1 7 1 73 A 1 58 1 6 A Starting current I Start max 3 5 A 3 5 A Condensate evaporator CM el Option 3 11 W A35 A35 ca 7 W Dimensions DTS 8 31E 23 DTS 8 31E 4 eight Width Depth 67 325 2 mm Weight 17 3 kg 25 3 kg CM Weight Option 5kg Installation position vertical Unit construction Standard steel O...

Page 43: ... 6 38 ated voltage 23 4 2 Power consumption A35 A35 P el 513 587 W 589 662 W Current consumption I nom max 3 1 3 37A 2 25 2 33 A Starting current I Start max 1 5 A 8 25A Condensate evaporator CM el Option 3 11 W A35 A35 ca 7 W Dimensions DTS 8241E 23 DTS 8241E 4 eight Width Depth 135 4 2 mm Weight 33 5 kg 41 2 kg CM Weight Option 5kg Installation position ertical Unit construction Standard steel O...

Page 44: ...6 38 ated voltage 23 4 2 Power consumption A35 A35 P el 596 678 W 632 7 9 W Current consumption I nom max 3 48 3 49 A 2 45 2 49 A Starting current I Start max 11 A 8 7 A Condensate evaporator CM el Option 3 11 W A35 A35 ca 7 W Dimensions DTS 8341E 23 DTS 8341E 4 eight Width Depth 135 4 2 mm Weight 34 1 kg 41 8 kg CM Weight Option 5kg Installation attitude ertical Unit construction Standard steel O...

Page 45: ...23 4 Power consumption A35 A35 P el 734 822 W 784 879 W Current consumption I nom max 5 8 5 97 A 5 1 5 29 A Starting current I Start max 15 A 11 8 A Condensate evaporator CM el Option 3 11 W A35 A35 ca 7 W Dimensions DTS 8441E 23 DTS 8441E 4 eight Width Depth 135 4 23 mm Weight 43 kg 5 7 kg Einbautiefe DTI Installation depth DTI 11 mm CM Weight Option 5kg Installation position ertical Unit constru...

Page 46: ...EC 6 38 ated voltage 23 4 2 Power consumption A35 A35 P el 1 68 1173 W 1 89 12 5 W Current consumption I nom max 7 9 8 4 A 7 7 44 A Starting current I Start max 18 4 A 13 8 A Condensate evaporator CM el Option 3 11 W A35 A35 ca 7 W Dimensions DTS 8541E 23 DTS 8541E 4 eight Width Depth 135 4 25 mm Weight 51 6 kg 65 kg CM Weight Option 5kg Installation position ertical Unit construction Standard ste...

Page 47: ...IEC 6 38 ated voltage 23 4 3 Power consumption A35 A35 P el 185 197 W 2 216 W 213 225 W 239 25 W Current consumption I nom max 11 5 A 7 5 A Starting current I Start max 3 A Condensate evaporator CM el Option 3 11 W A35 A35 ca 7 W Dimensions DTS 8841E 23 DTS 8841E 4 eight Width Depth 151 485 33 mm Weight 7 kg 75 kg CM Weight Option 5kg Installation attitude ertical Unit construction Standard steel ...

Page 48: ...ectrical components To facilitate installation with heavy units M8 eyebolt can be screwed into the upper fixing point on the top of the equipment housing Simple one man installation is thereby possible 9 2 Installation work The mounting surface of the switch cabinet is to be provided with cutout s and holes for air ventilation openings and for securing the unit according to cut out dimension 1 If ...

Page 49: ...nnected to the mains by means of a disconnecting device with a contact gap of at least 3mm when switch off No temperature regulator is allowed to be series connected to the cooling unit up stream feed The fuse as indicated on the name plate must be series connected as line protection ower connection and repairs if applicable may only be carried out by authorized trained electricians Power supply c...

Page 50: ...d with an electronic control system Internal temperature is measured by a temperature sensor The target setting point of the cooling unit can be set through operating display See Appendix I The cooling unit mustn t be switched on without the front cover on otherwise it will be damaged by poor heat dissipation 11 2 Operation display The cooling unit is provided with an operation display 0 0 is disp...

Page 51: ...external fan compressor all start up together 11 4 Door contact For safety reasons a door limit switch should be connected to the terminals provided on the cooling unit see the wiring diagram on housing cover or refer to circuit diagram With the switch in place when enclosure door is open thereby opening the switch all of the motors are turned off with a time lag In order to avoid any disruptive i...

Page 52: ...code refer to Appendix I 2 Parameter setting At home page firstly get into parameters t1 as described in iew arameters Then press select to show the value then press for 6S by pressing or to get the desired setting value now The value changes rapidly by continous press Then press Select again to confirm the change Press Mode to go back to previous menu or wait 5min to go back to home page If no ne...

Page 53: ...ly Avoid electrical shock revent damage to the heater exchangers Don t use any pointed or Sharp edged objects To prevent damage to the electrical connection on the inside of the covering hood the electrical plug in connections must be carefully removed before cleaning and reconnected after 13 2 Maintenance During equipment malfunction a fault alarm code will be shown on the display lease refer to ...

Page 54: ...r blocked 5 Check internal fan air channel 6 Check heat load Non authorized personnel should not repair the equipment 16 Warranty Conditions Warranty becomes null and void In case of improper usage of the unit noncompliance with operating conditions or non observance of instructions If operated in rooms in which corrosives or acids are present in the atmosphere In case of damage caused by contamin...

Page 55: ...ans ON 0 1 EFR External fan 0 means OFF 1 means ON 0 1 Con Compressor 0 means OFF 1 means ON 0 1 ALr Alarm 0 means alarm output 1 means units work normal 0 1 AL01 Sensor 1 error 0 means alarm 1 means normal 0 1 AL02 Cabinet door open 0 means alarm 1 means normal 0 1 AL03 High temperature 0 means alarm 1 means normal 0 1 Only t1 can be changed by user Others are for diagnosis reference The high tem...

Page 56: ...287 1077 邮箱 service pfannenberg cn http www Pfannenbergchina com Pfannenberg Electro Technology Suzhou Co Ltd No 108 Xinglin street SIP Suzhou 215026 Jiangsu P R C Tel 86 512 6287 1078 Fax 86 512 6287 1077 e mail service pfannenberg cn http www pfannenberg cn 685408017 11 2017 ...