Pfannenberg DTS 3241 Quick Manual Download Page 1

DTS 3241, 3261, and 3281 

Indoor and Outdoor Cooling Units 

Unpacking: 

Prior to and during unpacking make a visual inspection of the cooling unit 
to see whether any damage has occurred during transportation.  
 
Pay special attention to loose parts, dents, scratches, visible loss of oil etc.  
 
Any damage must be reported immediately to the delivering carrier.  
 
Save the carton and packaging material and request an inspection.  
 
Then file a claim with the delivering carrier. 
 
Before disposing of packaging material ensure that it does not contain any 
loose components. 

Danger! 

Burrs caused by production may be present on the metal edges of the 

unit. Always wear protective gloves when carrying out maintenance 

work and installation. In case of a warranty claim, exact details on the 

fault (photograph, if possible); the unit part number and serial number 

of the cooling unit are required. 

885408002 

Pfannenberg Inc. 

Subsidiary of the Pfannenberg Group 

68 Ward Road—Lancaster, NY 14086 

Phone: (716) 685-6866—Fax: (716) 681-1521 

www.pfannenbergusa.com 

Warranty Conditions:  

 

(WARRANTY IS VALID FOR 1 YEAR) 

 

Warranty becomes null and void: 

In case of improper usage of the unit, noncompliance with operating conditions 
or nonobservance of instructions. 
 
If operated in rooms in which corrosives or acids are present in the atmosphere. 
 
In case of damage caused by contaminated or jammed air filters. 
 
If a non-authorized person interrupts the cooling circulation, modifies the unit or 
changes the serial number. 
 
In case of damage caused by transport or by accidents. 
 
For the exchange of parts by non-authorized companies. 
 
In order to maintain your warranty rights please observe the following when 
returning the unit. 
 
Enclose an exact description of the fault in the shipping package. 
 
Enclose proof of delivery (delivery note or copy of invoice). 
 
Return the unit together with all accessories; use the original packaging or 
packaging of equivalent quality, send the unit freight prepaid and covered by an 
adequate transport insurance. 

Safety:  

Cooling units produced by Pfannenberg are designed for dissipating heat from 
switch cabinets. During each cooling process condensate can be produced. 
 
The cooling unit may only be used under the ambient conditions specified on 
the enclosed sheet. 
 
The cooling unit is to a large measure maintenance-free, (See Maintenance 
Section) 
 
Every other use is considered as non-authorized use making any warranty null 
and void. 
 
The electrical equipment must be regularly checked. Any faults such as loose 
connections or scorched cable must be removed immediately. 
 
Work on the cooling system and on electrical components may only be carried 
out by authorized specialist personnel. 
 
Compliance with applicable safety and environmental regulation is mandatory. 

Cleaning and Maintenance:

 

The cleaning intervals depend upon the relevant operating condi-
tions. In particular, observe the following instructions: 

Clean the heat exchanger regularly. 
 
Clean the heat exchanger using a soft brush or pressurized air.  
 
It is recommended that the condensate run off opening be checked  
regularly. 
 
If the cooling units are provided with a filter, clean the filter mat regularly. 
The cleaning intervals or the intervals for replacement of the filter mat 
mainly depends upon ambient conditions (air quality.) 
 
You can rinse the filter mat using water heated to 40 C and commercially 
available mild detergent.  
 
It is possible to remove any dirt by knocking the mat slightly, vacuum clean-
ing it or blowing it out.  
 
If the filter mat is oily or greasy, please replace.  

Caution! 

Protect the electric components against leakage. 

Do not use any pointed of sharp-edged objects. The ribs should not be 

compressed or damaged during the cleaning process. 

If the covering hood is removed, the electric plug-in connections on the 
inside must be removed by hand. During fitting do not forget to plug-in

Fault

 

Possible Cause

 

Remedy

 

Unit fails to 
cool. Internal 
fan is running.

 

 
Temperature setting to high.

 

 
Check temperature setting.

 

 
 
 
 
 
 
Unit fails  
to cool  
sufficiently.

 

Required cooling  
capacity exceeds capacity of 
unit. 

 

Dirty filter or condenser. 
                   
    

 

Lack of refrigerant. 

 
 

Internal and external fans not 
working. 

 

Air not circulating properly 
inside the switch cabinet. 

 
 

Check ambient temperature and 
internal load. 
 
 
Clean condenser. Clean or replace 
filter. 
 
Call authorized technician. Check 
unit for leaks. 
 
Call authorized technician. Check 
fan capacitors. Replace fans. 
 
Check enclosure and air circula-
tion inside enclosure. Air intake 
and exhaust must be unimpeded 
by components. 

Condensate 
accumulates 
in switch 
cabinet.

 

Exiting temperature is too 
low. Enclosure is not suffi-
ciently sealed. 

Set cooling unit to a higher tem-
perature setting. Close enclosure 
door and improve the seal in the 
enclosure. 

Condensate 
fails to drain.

 

Condensate drain is clogged. 

Clean condensate drainage. 
Condensate drainage hose must 
be inclined downward without 
showing a bend. 

Indication 
Faults LED: 
 
Door Contact 
 
High Pressure 
 
Start Up 

 
 
 
*C = Off, CF = Off, EF = Off 
 
*C = Off, CF = Off, EF = On 
 
*C = On, CF = On, EF = On 

 
 
 
**Sequence: 1, (Contacts Closed) 
 
***Sequence: 2, (Contacts Open) 
 
****Sequence: 3, (Contacts Open) 

 

 

 

Sequence 1: (User Error) 

Sequence 2: (Unit Fault) 

Sequence 3: (Test/start-up mode

*C = Compressor; CF = Condenser Fan; EF = Evaporator Fan 