Handling:
Storage:
Failure to observe these instructions will render the warranty provisions
null and void.
If it is necessary to store the air conditioner in a horizontal position prior to
mounting, make sure that it is placed in a vertical position for a minimum of
1 hour prior to starting the unit.
Running the compressor without oil in the compressor will cause perma-
nent damage to the air conditioner, and void the warranty of the unit.
TEST THE UNIT FOR FUNCTIONALITY PRIOR TO
MOUNTING THE AIR CONDITIONER ON THE
ENCLOSURE.
Technical Information:
Overall Dimensions: H x W x D: 515mm [25in] x 255mm [10in] x 266mm [10in]
DTS 3041/61/81:
(Voltage: 115V 60Hz / 100V 50Hz, Single Phase)
Amp Draw:
6.0
Capacity (95F/95F) [35C/35C]:
2700 BTUH [800 W]
Weight:
50 Lbs. [250 Kg]
DTS 3041/61/81:
(Voltage: 208-230V 60Hz / 230V 50Hz, Single Phase)
Amp Draw:
3.0
Capacity (95F/95F) [35C/35C]:
250 BTUH [730 W]
Weight:
50 Lbs. [25.0 Kg]
Overall Dimensions: mm [inches]
General Information:
Installation:
When tightening the bolts the gasket should be evenly compressed half the
thickness of the gasket.
Over compression of the gasket will not provide a better seal to the enclosure.
MAKE SURE NOTHING IS MOUNTED 6 INCHES IN FRONT OF INLET FAN.
CAUTION!
If the cooling unit is mounted on a switch cabinet door, it must be
confirmed that the hinge can support the additional weight or that the
switch cabinet will not topple over when the door is opened.
CAUTION!
Make cutouts required to the enclosure prior to mounting the air con-
ditioner. Make sure that metal particles are not allowed to enter the
enclosure.
Electrical Connection:
All power connections and repairs should be carried out by an authorized
trained electrician.
No other equipment should be connected to this circuit to prevent overloading.
Both main voltage and frequency must correspond to the nominal values indi-
cated on the nameplate of the cooling units.
ATTENTION!
THE COOLING UNIT MAY BE DAMAGED IF THE VOLTAGE IS TOO HIGH.
Testing and Startup Procedure:
Operating Conditions:
When unit is plugged in, the drawn-in switch cabinet internal air tempera-
ture is measured by a temperature sensor.
If the compressor and condenser fan do not turn on, adjust the thermostat
down to a lower setting that will call for the compressor and condenser
fan.
You should feel a temperature difference between the inlet and outlet air.
Door Contact: (All Units)
To avoid an increased production of condensate and for safety reasons a
door limit switch should be connected to the terminals provided (see
circuit diagram, housing cover or supplement.)
Centralized Fault Indication:
The signal of a fault in the cooling unit is caused by the high pressure
switch being opened.
This fault is displayed by the breaking of a potential-free contact.
Therefore, if the fault wire breaks, a fault signal will be simulated.
WARNING!
THE CONTACTS MAY BE LOADED WITH MAX. 230V, 10A.
Minimum Circuit Protection Class CC
NAME PLATE
125% of Run Load Amps
Short Circuit Protection for Units is 200 Amps
Hz
+ / - 3Hz
+ / - 10%
MAX 3.5mm [0.14”]
M
A
X
3m
m
[
0
.12”]
[Drilling Template Available on http://www.pfannenbergusa.com]
Mounting Insulation Installation:
Side Iso—Side Iso must be applied on
mounting holes on left and right sides.
Top Iso—Ensure notch and groove match
sides.
Must extend to side Iso mid unit and
bottom of unit.
Diagram A
“Q Mount”
Mounting Studs