background image

 

 

VersiStart i II   

 

 

 
 

5.

 

Adjustments 

08242.

B

1

2

3

7

8

6

5

4

 

 

 

  Current Ramp 
  Current Limit 
  Motor Trip Class 
  Motor FLC 
  Soft Stop Time 
  Excess Start Time 
  Auxiliary Relay Function 
  Phase Sequence Protection 

 

 

  

  Current Ramp 

 

 

 

08244.

A

 

Select the initial start current (A) and ramp time (B). 

Current ramp starting extends the time soft starter 

takes to reach the current limit and is suitable for 

generator set supplies, loads requiring an extended 

start time or applications with extreme load 

variation between starts. 

The ramp time does not control the time the motor 

will take to reach full speed. 

Cu

rren

 

Time 

  Current Limit 

 

 

 

08245.

A

 

Select the current limit (C). 

The current limit is the maximum level of current 

the soft starter will deliver to the motor during the 

soft start. 

Cu

rren

 

Time 

  Motor Trip Class 

 

 

 

08246.

A

 

Select the trip class for motor overload protection. 

The trip class reflects the maximum time (in 

seconds) that the motor can run at locked rotor 

current.  The Motor Trip Class setting assumes a 

locked rotor current of 600%. 

 

Setting the motor trip class to "Off" disables motor 

overload protection. 

 

  Motor FLC 

 

 

 

08247.

A

 

Configure the soft starter to match the motor's full 

load current (FLC). 

Configure according to the motor's nameplate 

current. Divide the motor's FLC by the soft starter's 

maximum current rating (on the soft starter's 

nameplate label). 

0

8

2

3

9

.A

INPUT RATING:

200-440VAC, 50/60Hz, 3PH

OUTPUT FLC:

xxAAC53b4-6:354, 30 kW @ 400V

AUXILIARY CONTACTS: 5A@ 250VAC/360VA, 5A @30VDC Resistive

WITHSTAND CURRENT: 5000ARMS, 600VAC max.

POWER CONTACTS:

#10 - #2AWG, 6 - 35 mm2(3-5 Nm, 2.2-3.7 lb-ft)

AUXILIARY CONTACTS: 20 - 16AWG, 0.75- 1.5 mm2(0.5 Nm, 4.5 lb-in)

Motor FLC

Soft starter FLC

 

Summary of Contents for VersiStart i II

Page 1: ...ion 4 3 1 Dimensions and Weights 4 3 2 Physical Installation 4 4 Electrical Installation 5 4 1 Power Terminations 5 4 2 Control Voltages 5 4 3 Control Circuits 6 4 4 Outputs 7 4 5 Electrical Schematic...

Page 2: ...Only a qualified electrician should carry out the electrical installation Improper installation of the motor or the VersiStart i II may cause equipment failure serious injury or death Follow this manu...

Page 3: ...and 2014 35 EU Low voltage directive is not proved The devices of the VersiStart i II series are electrical equipment that is used in industrial electrical power installations They are designed for a...

Page 4: ...VS i II 170 200 160 240 216 214 114 5 51 6 5 VS i II 200 7 87 6 30 9 44 8 50 8 43 4 5 2 0 14 33 3 2 Physical Installation 1 2 3 4 08241 D VS i II 018 VS i II 100 Allow 100 mm 3 9 inch between soft st...

Page 5: ...428 A 6 mm 0 24 inch Torx T20 3 Nm 2 2 ft lb Torx T20 4 Nm 2 9 ft lb n a n a 7 mm 3 Nm 2 2 ft lb 7 mm 4 Nm 2 9 ft lb n a 3 5 mm 0 5 Nm max 4 4 in lb max 4 2 Control Voltages VersiStart i II soft start...

Page 6: ...trol input terminals 01 02 Two wire control Three wire control 110 240 VAC 24 VAC VDC A3 A1 A2 01 02 A3 A1 A2 01 02 1 1 03241 D A3 A1 A2 01 02 A3 A1 A2 01 02 2 3 2 3 03242 E 380 440 VAC Start stop To...

Page 7: ...shunt trip mechanism of an upstream circuit breaker in order to isolate the motor branch circuit or to signal the trip to an automation system or externally The relay will open when the trip is reset...

Page 8: ...the motor during the soft start Current Time Motor Trip Class 08246 A Select the trip class for motor overload protection The trip class reflects the maximum time in seconds that the motor can run at...

Page 9: ...ed time E Current Time Auxiliary Relay Function 08250 A Select the function of the soft starter s programmable output terminals 23 24 When set to Run the relay will operate when the soft start is comp...

Page 10: ...thermistor connection B4 B5 Allow motor to cool x 5 Current imbalance Check for mains supply or line current imbalance L1 L2 L3 x 6 Supply Frequency Check mains voltage is available and supply freque...

Page 11: ...and low frequency limits both apply with no time delay A supply frequency trip will also occur if all three input phases are lost while the soft starter is running all three input phases fall below 12...

Page 12: ...n Modules VersiStart i II soft starters support network communication via easy to install communications modules Each soft starter can support one communications module at a time Available protocols E...

Page 13: ...0 VAC and 5 6 k 24 VAC VDC Outputs Main contactor relay terminals 13 14 Normally open 6 A 30 VDC 6 A 250 VAC resistive Programmable relay terminals 23 24 Normally open 6 A 30 VDC 6 A 250 VAC resistive...

Page 14: ...ics and distortion IEC61000 2 4 Class 3 EN IEC61800 3 Short Circuit Rated short circuit current VS i II 018 to VS i II 048 5 kA 1 Rated short circuit current VS i II 060 to VS i II 200 10 kA 1 1 These...

Page 15: ...C 50 C VS i II 018 18 A 17 A 17 A 15 A VS i II 034 34 A 32 A 30 A 28 A VS i II 042 42 A 40 A 36 A 33 A VS i II 048 48 A 44 A 40 A 36 A VS i II 060 60 A 55 A 49 A 45 A AC53b 4 6 594 1000 metres AC53b 4...

Page 16: ...URD30xxxA0160 A070URD30xxx0160 170M 1318 160 FEE VS i II 048 15000 6 6URD30xxxA0160 A070URD30xxx0160 170M 1318 180 FM VS i II 060 18000 6 6URD30xxxA0160 A070URD30xxx0160 170M 1319 180 FM VS i II 075 5...

Reviews: