background image

PERTRONIC INDUSTRIES LTD 

INSTALLATION / OPERATING INSTRUCTIONS 

Loop Responder (For PCB versions 2.30 and greater) 

Pertronic Industries Ltd 

1 of 2 

Loop Responder Issue2 Sept 2002 

 

Overview 

The 

Loop Responder

 is used primarily to interface zones of conventional detectors into 

Pertronic

 

analogue addressable fire alarm systems. Other uses include monitoring the interference switches 
of sprinkler valves, reading the fault and alarm status from Vesda systems, or receiving commands 
from a SCADA system. 

Additionally, the 

Loop Responder

 has a set of clean change-over contacts that can be utilised by 

the panel and mapped as a loop relay. 

The 

Loop Responder

 uses 9 module loop addresses—the first eight for input circuits 1 to 8, and 

the ninth for the relay. 

A limited number of 

Loop Responders

 may be powered from the loop; when larger numbers are 

required, they may be powered from a supply or supplies that must be electrically isolated from the 
panel supply. 

Addressing 

Select the base address (01 to 91) using the two loop address switches labeled 

ADDRESS

 located 

at the bottom-right of the PCB. (Refer to the diagram overleaf.) 

The 

Loop Responder

 uses 9 module loop addresses: the first or base address for Circuit1; the 

second address (base a 1) for Circuit 2; and so on to the eighth address for Circuit 8 (base 
a 7). The ninth address (base a 8) is assigned to the output relay. 

Each loop can have a maximum of 100 modules (addresses 00 to 99), so the highest base address 
the 

Loop Responder

 can have is 91. 

Smoke Detector or Switch Input Selection 

Link 

LK1

, located at the center-bottom of the 

Loop Responder

 PCB (refer to the diagram 

overleaf), is used to select the function of the inputs. 

When 

LK1

 is removed, normal conventional circuit operation is used for all 8 circuits—for 

using smoke detectors, indicating heat detectors, and manual call points. 

When 

LK1

 is inserted, 

switch input

 operation is used for all 8 circuits. This mode of operation 

allows the use of switch or contact opens and closures for the alarm states. 

Loop and External Power Supply 

Switch 

S1

, located at the top RHS of the 

Loop Responder

 PCB, is used to select external or loop 

powering of the detector circuits. The micro-processor and loop interface components are always 
powered from the loop, but, by using 

S1

, either the loop or an external supply can be selected to 

power the detector or switch circuits. The purpose of this is to conserve the power requirement from 
the loop when a number of Loop Responders are used together. 

The maximum loop current allowed for all connected loop devices is 350mA per loop. 

When the switch is pushed to the right—to the 

Loop Power

 position, the loop supplies the power to 

the circuits. 

When the switch is pushed to the left—to the 

External Power

 position, the external supply provides 

the power to the circuits.

 

 

Loop Powered Connection   

 

 

Externally Powered Connection 

 

Reviews: