Return to
For temperature to resistance values when trouble-
shooting probe or temperature issues.
Table 8-21. Temperature – Resistance Values
\
To replace temperature probe, refer to section
8.6.3.
Electrical System Repair Instructions
Page 8-32
TEMPERATURE
(°C)
TEMPERATURE
(°F)
RESISTANCE
(OHMS)
-30
-22
111300
-25
-13
86430
-20
-4
67770
-15
5
53410
-10
14
42470
-5
23
33900
0
32
27280
5
41
22050
10
50
17960
15
59
14690
20
68
12090
25
77
10000
30
86
8313
35
95
6940
40
104
5827
45
113
4911
50
122
4160
55
131
3536
Residential Refrigeration
and Front Venting Commercial Refrigeration
Service Manual
STEP 5.
Temperature
Probe
Reverse this instruction to connect the replacement
controller.
8.6.4
Temperature Probe
Each refrigerated zone has one 10K ohm NTC probe,
which senses compartment temperature. Sensing
probe is located behind the control cradle or next to
the evaporator fan behind the cover panel. Defrost
termination probe (evaporator). Additionally, low
temperature products may have a defrost
termination probe inserted into the fins of the
evaporator.
Figure 8-17. Temperature Probe