Workshop Manual, TPD 1458E, issue 3 - Perkins Confidential: Green
400 Series
Wiring diagram - automatic shutdown 55 amp alternator 403C-15, 404C-22
and 404C-22T
Automatic shutdown operating conditions
If the conditions listed below continues for more than ten seconds while starting, or two seconds while the
engine is being operated, the engine will shutdown.
If the water temperature exceeds 110 °C (230 °F) ± 3°C (5 °F)
If the oil pressure falls below 0,3 kgf / cm² (4.27 lbf / in² top cover option) or 1,0 kgf / cm² (14.22 lbf / in² oil rail
option).
Cautions:
l
There is no automatic shutdown for low water levels.
l
Diode capacity: current 3 amps, reverse voltage 600V, this is mandatory.
Notes:
l
Maximum current draw for the standard oil pressure switch is 0.42 amps (5 Watts maximum bulb).
l
A delay fuse can be fitted if necessary.
K1094/2
Glow signal
Key switch
AC
30
17
19
50
*1
6
4
5
1
2
3
Oil Press.
switch
Oil press.
Altr.
*2 Diode
Water temp.
*2 Diode
D1
D2
Solenoid switch
Glow Plugs
Fuse
Automatic
shutdown
device
Thermo
B
S
Starter motor
12V
Battery
W
B+
B
Alternator
11
Ind
*3
65A 80/0.4 (10)