Operation
DK58113 Developer Kit User Manual
33
2
2.5.1.2
DC Bus Current Limits
The following MC58113 DC bus current limits are required to safely operate the DK58113 board:
Note that these values are designed to protect the DK58113 circuitry. Lower values may be used to protect the motor.
If an Atlas amplifier is used these DC bus current scale and limit values do not need to be set.
All of the MC58113 parameters described in this section can be conveniently specified using Pro-Motion via the Axis
Wizard. See
1.12, “First-Time System Verification”
2.5.2
DC Bus Voltage Monitoring
DK58113 monitors the main DC bus voltage for overvoltage and undervoltage conditions. These thresholds are user-
settable within the voltage operating range of the drive. DC bus voltage monitoring may operate even when a remote
amplifier is used, as long as the +HV supply is still connected to the DK58113.
2.5.2.1
DC Bus Voltage Monitoring Scale Values
To correctly monitor the DK58113 DC bus voltage it is necessary to know the DC bus voltage scale factor. The
following table provides this value.
2.5.2.2
DC Bus Voltage Limits
The following MC58113 DC bus voltage limits are required to safely operate the DK58113 board:
Note that these values are designed to protect the DK58113 circuitry. More restrictive values may be used to protect
the motor.
All of the MC58113 parameters described in this section can be conveniently specified using Pro-Motion via the Axis
Wizard. See
1.12, “First-Time System Verification”
2.5.3
Shunt Resistor & Diode
J14 provides a connection for a shunt resistor and diode that may be used to regulate overvoltage conditions on the
DC bus. Such conditions can occur during deceleration of a motor with a large inertia.
Parameter
Value & Units
Comments
Bus Current Supply Limit
20.0 A
This value should be entered to ensure safe
operation of the DK58113.
Bus Current Return Limit
20.0 A
This value should be entered to ensure safe
operation of the DK58113.
DC bus current monitoring functions will not work when a remote amplifier is used.
Parameter
Value & Units
Comments
Bus Voltage Display
.966 mV/count
This value should be entered so that the DC bus voltage
can be traced and displayed correctly in volts.
Parameter
Value & Units
Comments
Undervoltage Limit
10.0 V
This value should be entered to ensure safe
operation of the DK58113.
Overvoltage Limit
60.0 V
This value should be entered to ensure safe
operation of the DK58113.