AS-i/PROFIBUS-Gateway
Command Interface
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Is
s
ue dat
e -
12.
8.
2007
79
Cok Config_Ok
AAe Auto_Address_Enable
OL
Offline
DX
Data_Exchange_Active
10.3.4.3
Get Flags (GET_FLAGS)
With this call, the following entry is read out of the AS-i/PROFIBUS Gateway: the
flags according to the AS-i slave specification.
Pok Periphery_Ok
This flag is set when no AS-i slave is signaling a peripheral fault.
S0
LDS.0
This flag is set when an AS-i slave with address 0 exists.
AAs Auto_Address_Assign
This flag is being set when the automatic address programming is possible
(in other words, AUTO_ADDR_ENABLE = 1; no "incorrect" slave connected
to the AS-i).
AAv Auto_Address_Available
This flag is set when the automatic address programming can be executed,
exactly one AS-i slave is currently out of operation.
CA
Configuration_Active
The flag is set in configuration mode and reset in protected mode.
NA
Normal_Operation_Active
This flag is set when the AS-i master is in normal operation.
APF AS-i Power Fail
This flag is set when the voltage on the AS-i cable is too low.
OR
Offline_Ready
The flag is set when the offline phase is active.
Request
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
47
16
2
T
–
circuit
Response
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
47
16
2
T
response
3
Pok
4
OR
APF
NA
CA
AAv
AAs
S0
Cok
5
–
AAe
OL
DX