background image

VBA-4E3A-G20-
ZEL/M1L-P2

AS-Interface
Motor Control Module

FACTORY AUTOMATION

MANUAL

Summary of Contents for VBA-4E3A-G20-ZEL/M1L-P2

Page 1: ...VBA 4E3A G20 ZEL M1L P2 AS Interface Motor Control Module FACTORY AUTOMATION MANUAL...

Page 2: ...of Delivery for Products and Services of the Electrical Indus try published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its mos...

Page 3: ...Use and Application 7 4 2 Housing 8 4 3 Indicators and Operating Controls 9 4 4 Interfaces and Connections 11 5 Installation 13 5 1 Storage and Transport 13 5 2 Unpacking 13 5 3 Connecting the AS Int...

Page 4: ...ntire range of device functions Avoid faulty operation and associated faults Reduce costs associated with downtime and incidental repairs Increase the effectiveness and operating efficiency of your pl...

Page 5: ...e developed and manufactured under observance of the applicable European standards and guidelines The product manufacturer Pepperl Fuchs GmbH 68307 Mannheim has a certified quality assurance system th...

Page 6: ...cation and or repair are dangerous and will void the warranty and exclude the manufacturer from any liability If serious faults occur stop using the device Secure the device against inadvertent operat...

Page 7: ...two inputs for three wire sensors with positive switching output PNP or for mechanical contacts The input characteristic of the inputs corresponds to type 1 according to EN 61131 2 The motors and the...

Page 8: ...flat cable Function displays for the bus external auxiliary power status information inputs and outputs Communication monitoring Configurable start stop ramps for motor control Supply of the connected...

Page 9: ...start stop ramps see Configuration of Start Stop Ramps in the Commissioning chapter Start Stop Ramp Display YELLOW ASI BLACK AUX PWR FAULT AUX FUSE1 FUSE2 DIR MOT1 MOT2 ERR1 ERR2 IN1 IN2 IN1 MOT1 IN2...

Page 10: ...OK Flashes On Address 0 On On AS Interface communication error Flashes Flashes Peripheral fault collective error message for AUX external auxiliary power is missing or is inverted Overload of the sen...

Page 11: ...Inputs 4 4 Interfaces and Connections Flat Cable Specification The AS Interface motor control module is compatible with the AS Interface standard cable in accordance with IEC 62026 2 LED MOT1 LED MOT2...

Page 12: ...rl Fuchs Designation Color Sheathing material wire insulation Cross section UL Cable Style Approval VAZ FK R YE Yellow TPE TPE 2x 1 5 mm 2103 VAZ FK R BK Black TPE TPE 2x 1 5 mm 2103 VAZ FK PUR YE Yel...

Page 13: ...he AUX auxiliary power The permissible auxiliary power is 18 V 30 V Contact between the motor control module and flat cables is established via two metal mandrels and using insulation piercing technol...

Page 14: ...lower guide see the module tag Black AUX 3 Insert the yellow AS Interface flat cable with the profile edge 3 to the motor control module into the upper guide see the module tag YELLOW 4 Make sure that...

Page 15: ...e profile edge 3 to the motor control module into the lower guide see the module tag Black AUX 3 Insert the yellow AS Interface flat cable with the profile edge 2 to the motor control module into the...

Page 16: ...on the reverse polarity protection 1 with a curvature which means that the cable guide cannot be closed completely mechanical reverse polarity protection Figure 5 3 Flat cable inserted incorrectly pr...

Page 17: ...EED control signal the motor control module actuates the respective motor switched on with an analog voltage value The SPEED control signal is released only when DO0 or DO1 data bit is set for the rel...

Page 18: ...trol limits are exceeded due to an excessive load the motor control module issues a peripheral fault Parameter Bits P0 P2 Reporting a Motor Fault DI0 DI1 The motor control module records a motor fault...

Page 19: ...re constant for each of the eight ramps and independent of the set speed The reference value for all ramps is the speed signal SPEED 10 V For a lower parameterized speed the ramp duration is proportio...

Page 20: ...parameter values to the motor control module to activate configuration mode max 10 s DO0 DO2 must have the value 4 in each step If the parameter sequence was correct the motor control module responds...

Page 21: ...e step configuration process Fault Scenarios Step DO0 DO2 P0 P2 DI0 DI3 Comment 4 x x Motor control module in normal mode 1 4 3 x Start activation sequence for configuration mode 2 4 1 x 3 4 6 x 4 4 3...

Page 22: ...of the motor supply Replace the motor control module cannot be repaired and remove the cause of the overload before starting the motor again Note Fault information via AS Interface via DI0 motor 1 da...

Page 23: ...chs GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com USA Headquarters Pepperl Fuchs Inc Twinsburg Ohio 44087 USA Tel 1 330 4253555 E mail sales us pepperl fuchs com Asia P...