Product Description
2
0
1
8
-0
6
19
LEDs for PWR, MOT1, MOT2, ERR1, ERR2, IN1, IN2
Status LEDs for zone coupling: Conveyor direction from left to right
Note!
Motor Fuses Are Safety Fuses
For protection against short circuits, each DC roller motor is secured with its own safety fuse
with a 5 A rated current. The fuses are not interchangeable. If a fuse is faulty, the module must
be replaced.
LED
Color
Description
PWR
Green
■
On = Power supply is OK
■
Off = Power supply is not OK
MOT1
Yellow
Operating status of DC roller motor 1:
■
On = Motor is active
■
Off = Motor is at a standstill or running down as per set start/stop
ramp
MOT2
Yellow
Operating status of DC roller motor 2:
■
On = Motor is active
■
Off = Motor is at a standstill or running down as per set start/stop
ramp
ERR1
Yellow
Fault status of DC roller motor 1:
■
On = Motor fault or no motor connected
■
Flashing = Motor fuse 1 of the motor control module is faulty
■
Off = No motor fault
ERR2
Yellow
Fault status of DC roller motor 2:
■
On = Motor fault or no motor connected
■
Flashing = Motor fuse 2 of the motor control module is faulty
■
Off = No motor fault
IN1
Switch state of zone sensor 1:
■
On = Zone sensor has detected conveyed product (high level)
■
Off = Zone sensor has not detected any conveyed product (low
level)
IN2
Switch state of zone sensor 2:
■
On = Zone sensor has detected conveyed product (high level)
■
Off = Zone sensor has not detected any conveyed product (low
level)
Table 2.3
LED
Color
Description
X1 IN
Yellow
Input from interface 1: Status of zone sensor of upstream zone
■
On = Zone sensor has detected conveyed product (high level)
■
Off = Zone sensor has not detected any conveyed product (low
level)
X1 OUT
Yellow
Output from interface 1: Release signal for upstream zone
■
On = Release signal for upstream zone has been set (high level)
■
Off = Release signal for upstream zone has not been set (low
level)