Mounting set

• Ordering code 103005469

• Alternative use of the mounting plates or ferrules

•  Mounting plates: 2 pieces for mounting on non-linear stable basis,  

e.g. on groove rails/profiles

•  Ferrules: 4 pieces for insertion to secure the screw fixings to the 

mounting surface for applications with regular high temperature 

variations

4.  Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by  

authorised personnel in a de-energised condition.

The connection to the AS-Interface system is realised through an M8 

or M12 connector. The connectors are A-coded. The connection to 

the M12-plug is made (according to EN 62026-2) to the AS-Interface 

systems with an adapter cable of M8 / 4-pin (socket) on to M12 / 4-pin 

(plug):

Pin assignment M8 / M12 connector

spare

3

2

1

4

AS-i -

AS-i +

spare

Connector adapter cables (available as accessories)

IP67, M8-coupling to M12-connector, 4-pin

Cable length

Ordering code

1 m

103003648

2 m

103003649

3 m

103003651

5.  Functions and configuration

5.1  Programming the slave address

The slave address is programmed through the M8 connector. Any 

address from 1 to 31 can be set by means of the AS-i bus master or a 

hand-held programming device.

5.2  Configuration of the safety monitor

The RSS260 AS can be configured in the ASIMON configuration 

software with the following monitoring devices (also refer to the 

ASIMON manual). (also refer to the ASIMON manual) 

Double channel dependent

• Synchronisation time: 0.1 s

• Optionally with startup test

• Optional with local acknowledge

The configuration of the safety monitor must be tested and 

confirmed by a qualified and authorised safety expert/safety 

engineer.

5.3  Status signal "safety release"

The "safety release" status signal from a Safety at Work slave can be 

cyclically queried by the control system through the AS-i master. To 

thiseffect, the 4 input bits with the varying SaW code of a Safety at 

Work slave are evaluated through an OR operation with 4 inputs in the 

control system.

5.4  Actuator teaching / actuator detection

Safety sensors with standard coding are ready to use upon delivery.

Individually coded safety sensors and actuators will require the 

following "teach-in" procedure: 

1. Switch the safety sensor's voltage supply off and back on.

2.  Introduce the actuator in the detection range. The teach-in procedure is 

signalled at the safety sensor, yellow LED flashes (1 Hz).

3.  After 10 seconds, brief cyclic flashes (3 Hz) request the switch-off 

of the operating voltage of the safety sensor. (If the voltage is not 

switched off within 5 minutes, the safety sensor cancels the "teach-

in" procedure and signals a false actuator by 5 yellow flashes.)

4.  After the operating voltage is switched back on, the actuator must be 

detected once more in order to activate the taught actuator code. In 

this way, the activated code is definitively saved!

For ordering suffix -I1, the thus executed allocation of safety sensor and 

actuator is irreversible.

For ordering suffix -I2, the "teach-in" procedure for a new actuator can be 

repeated an unlimited number of times . When a new actuator is taught, 

the code, which was applicable until the moment, becomes invalid. 

Subsequent to that, an enabling inhibit will be active for ten minutes, thus 

providing for an increased protection against tampering. The AS-i Duo 

LED will flash red/green until the expiration of the time of the enabling 

inhibit and the detection of the new actuator. In case of power failure 

during the lapse of time, the 10-minutes tampering protection time will 

restart.

Actuator detection (AD)

Device with actuator detection (AD) can emit the number of especially 

coded actuators through the parameter port. 

In this way, a non-safe identification of the actuator is possible. 

Through the 4 bits of the parameter port, the actuators with the 

numbers 01 - 15 can be detected and transmitted to the control. 

If no actuator is detected, a 0 will be emitted.

Safety sensors and actuators with actuator detection must always be 

used in pairs.

Actuator RST260-1-AD01…15, 15 different actuators at the most

Summary of Contents for schmersal RSS260 AS

Page 1: ...responsibility of the manufacturer of a machine or plant to ensure the correct functionality of the entire machine or plant The safety switchgear must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description Content 1 About this doc...

Page 2: ...ronic safety sensor is designed for application in safety circuits and is used for monitoring the position of movable safety guards In this application the safety sensor monitors the position of hinged sliding or removable safety guards by means of the coded electronic actuator The safety function consists of safely switching off the code transmission when the safety guard is opened and maintainin...

Page 3: ...essly approved by K A Schmersal GmbH Co KG could void the user s authority to operate the equipment L émetteur récepteur exempt de licence contenu dans le présent appareil est conforme aux CNR d Innovation Sciences et Développement économique Canada applicables aux appareils radio exempts de licence L exploitation est autorisée aux deux conditions suivantes 1 L appareil ne doit pas produire de bro...

Page 4: ... the yellow LED signals the actuator detection the flashing of the yellow LED after a delay signals that the safety sensor is actuated in the hysteresis area Recommended Adjustment Align the safety sensor and actuator at a distance of 0 5 x sao The correct functionality of both safety channels must be checked by means of the connected safety monitoring module 3 5 Dimensions All measurements in mm ...

Page 5: ...varying SaW code of a Safety at Work slave are evaluated through an OR operation with 4 inputs in the control system 5 4 Actuator teaching actuator detection Safety sensors with standard coding are ready to use upon delivery Individually coded safety sensors and actuators will require the following teach in procedure 1 Switch the safety sensor s voltage supply off and back on 2 Introduce the actua...

Page 6: ...Off 1 static 0 Internal device error periphery error red green flashing Flashes 1 1 static 0 AS i error slave address 0 or communication error red depending on the condition 0 static 0 1 refer to flash code Table 2 Error messages flash codes yellow LED Flash codes yellow Designation Autonomous switch off after Error cause 4 flash pulses Ambient temperature high 0 min Ambient temperature too high T...

Page 7: ...nctionality A regular visual inspection and functional test including the following steps is recommended 1 Check the safety function 2 Check the fixing and integrity of the safety switchgear the actuator and the cable 3 Remove possible metal chips Measures must be taken to protect against manipulation or against the bypassing of safety device for example using an extra actuator Damaged or defectiv...