Pulscon LTC57 PROFIBUS PA
Commissioning (via operating menu)
2015
-0
3
69
8. Navigate to: Setup menu
Distance.
Displays the distance D between the reference point R and the level L.
9. Navigate to: Setup menu
Signal quality.
Displays the signal quality of the level echo.
10. For operation via local display:
Navigate to: Setup menu
Mapping
Mapping
Confirm distance
Compare the displayed distance to the real distance in order to start the recording of the
mapping curve if required.
11. For operation via operating tool:
Navigate to: Setup menu
Mapping
Confirm distance
Compare the displayed distance to the real distance in order to start the recording of the
mapping curve if required.
10.4
Recording the reference curve
After the configuration of the measurement it is recommended to record the current envelope
curve as a reference curve. The reference curve can be used later on in the process for
diagnostic purposes. To record the reference curve use the
Save reference curve
parameter.
Navigation
: Expert
Diagnostics
Envelope diagnostics
Save reference curve
Meaning of the options
• No
No action
• Yes
The current envelope curve is saved as reference curve.