Power Supply PS1000-A6-24.20
Output
8
Output
The output provides a SELV/PELV/EST1 rated voltage, which is galvanically isolated
from the input voltage.
The output is designed to supply any kind of loads, including capacitive and inductive loads.
If extreme large capacitors, such as EDLCs (electric double layer capacitors or
UltraCaps
)
with a capacitance >1F are connected to the output, the unit might charge the capacitor
in an intermittent mode.
The output is electronically protected against overload, no-load and short-circuits.
In case of a protection event, audible noise may occur.
Output voltage
nom.
24V
Adjustment range
24-28V
Guaranteed value
max.
30V
This is the maximum output voltage which can occur
at the clockwise end position of the potentiometer
due to tolerances. It is not a guaranteed value which can
be achieved.
Factory settings
typ.
24.1V
±0.2% in
Single Use
mode at full load, cold unit
typ.
24.1V
±0.2% in
Parallel Use
mode at 20A, cold unit (results to
typ.
23.9V
±0.2%
at 24A and typ. 25.1V
±0.2%
at no load)
Line regulation
max.
10mV
Between 90 and 300Vac input voltage change
Load regulation
max.
100mV
Between 0 and 24A in
Single Use
mode, static value
typ.
1000mV
Between 0 and 20A in
Parallel Use
mode, static value,
see Figure 8.2
Ripple and noise voltage max.
50mV
pp
Bandwidth 20Hz to 20MHz, 50Ohm
Output current
nom.
24 A
1
At 24V and ambient temperatures below +45°C,
see Figure 18.1
nom.
20A
At 24V and +60°C ambient temperature, see Figure 8.1
nom.
15A
At 24V and +70°C ambient temperature, see Figure 18.1
nom.
20.6 A
1
At 28V and ambient temperatures below +45°C,
see Figure 18.1
nom.
17.1A
At 28V and +60°C ambient temperature, see Figure 8.1
nom.
13A
At 28V and +70°C ambient temperature, see Figure 18.1
Derate b45°C and +70°C
Fuse breaking current
typ.
60A
Up to 12ms once every five seconds, see Figure 8.2
The fuse braking current is an enhanced transient current
which helps to trip fuses on faulty output branches.
The output voltage stays above 20V.
Overload behavior
Continuous current
For output voltage above 13Vdc, see Figure 8.1
Interm
ittent current
2
For output voltage below 13Vdc, see Figure 8.1
Overload/
max.
29.8A
Continuous current, see Figure 8.1
short-circuit current
typ.
29A
Intermitted current peak value for typ. 2s
Load impedance 10mOhm, see Figure 8.2.
Discharge current of output capacitors is not included.
max.
9.8A
Intermitted current average value (R.M.S.)
Load impedance 10mOhm, see Figure 8.2.
Output capacitance
typ. 8500μF
Included inside the power supply
Back-feeding loads
max.
35V
The unit is resistant and does not show malfunctioning
when a load feeds back voltage to the power supply.
It does not matter whether the power supply is on or off.
The absorbing energy can be calculated according
to the built-in large sized output capacitor.