PROFIBUS Commissioning
2
016-
06
33
6
PROFIBUS Commissioning
6.1
Device Type Manager (DTM): Installation and Commissioning
System requirements for installation, commissioning, and operation of the DP/PA gateway
device type manager (DTM):
■
Hardware requirements based on your FDT frame application
■
FDT frame application (FDT specification 1.2)
■
Latest version of the HD2-GTR-4PA.PN DTM
■
40 MB free hard drive storage
Installing the DTM Package with PACTware
TM
(Example)
In order to install the DTM package on your system, proceed as follows:
1. Install the P+F-FieldConnex
®
DTM package.
2. Start the PACTware
TM
program.
3. Update the device catalog.
The
Create new device catalog
window appears:
4. Confirm with
Yes
.
The device catalog is installed and ready for operation.
6.2
PROFINET DTM Project
This section explains how to generate a project tree, using PACTware
TM
as an FDT example.
Creating the PROFINET DTM Project Tree
In order to create the PROFINET DTM project tree, proceed as follows:
1. Start PACTware
TM
.
Note: Make sure the latest DTM version is installed and that the device catalog is updated.
2. In order to view the project tree, choose
View > Project
. Alternatively, press <F2>.
3. Open the appropriate project or create a new one via
File > New
or
File > Open
.
4. Open the Device catalog:
View > Device Catalog
. Alternatively, press <F3>.
5. Open the menu entry FUCHS GmbH.
Note!
Sometimes, the FDT application does not immediately display the address change in the
project window, even though the change has been made. If that happens, save the project
once to refresh the display.