IO-Link Programming
2
0
1
9
-0
2
17
■
Revision Information:
Displays the firmware and hardware version. Please have this
information ready when contacting our Service Center. These are read-only fields.
7.1.2
"Parameter" Menu Item
Figure 7.2
Menu item
Parameter
All switching signals as well as the analog signal can be parameterized and configured in the
"Parameter" menu item. The "Parameter" menu item is divided into five areas:
■
Operation Parameter:
Here you can set the switch points and limit values for the
switching signal and the analog signal. The output operating modes are configured in the
"Operation Mode Configuration" item.
■
Teach-In Parameter:
Here you can manually teach in the switching signals. To do this,
place the damping element in the required position and teach in this position for the
relevant switch point. The parameters are adopted permanently using system command
64 (Adopt Teach-in).
■
Operation Mode Configuration:
Here you can configure the switching and analog
signals. Five switching signal modes (see chapter 11.2), inverted or non-inverted
switching signal logic, switching signal hysteresis of 0 (normal) up to 2 (high), and the
window width are available.
■
Event Configuration:
Here you can set whether or not instances of the damping element
leaving the sensing range are logged as an error.
■
Output Configuration:
Here you can set the output type for Q1 and Q2 (push-pull,
sinking, sourcing).