![Pepperl+Fuchs LAL-SRW series Manual Download Page 27](http://html.mh-extra.com/html/pepperl-fuchs/lal-srw-series/lal-srw-series_manual_1527674027.webp)
WARNING DEVICE LAL-SRW
Operation
23
3717
20
11-
05
EN - 25
EN
5
Operation
5.1
Alarm Signals
The warning device indicates an alarm status or sensor fault both visually and
acoustically. The respective "OVERFLOW ALARM" or "HIGH OIL LEVEL"
("SLUDGE ALARM") LEDs are illuminated until the system returns to a normal
status.
5.2
Resetting the Alarm Signal
Pressing the "ALARM RESET" button resets an alarm that occurred in the past
(flashing green LED).
If the alarm status is still active, pressing the "ALARM RESET" button resets the
acoustic alarm and the relevant relay. The sensor LEDs remain lit/continue to
flash.
If the DIP switch "Repeat alarm in 24 hours" is set to ON (see chapter 4.1), the
alarm is repeated after 24 hours.
LED
Status
Meaning
Yellow LED "SUPPLY"
lights up
The device is connected to the power supply.
Device in operation
flashes
Commissioning the overflow sensor
Green LED
"SYSTEM OK"
lights up
No errors or alarms active
–
normal operation
flashes
No alarm or error active, there was an alarm or
error in the past.
Red LED
"OVERFLOW ALARM"
lights up
Alarm active, overflow sensor is covered with
liquid.
flashes
Internal sensor fault, lead breakage or short-
circuit
Red LED
"HIGH OIL LEVEL"
lights up
Alarm active, oil level sensor is covered with oil.
flashes
Internal sensor fault, lead breakage or short-
circuit
Red LED
"SLUDGE ALARM"
lights up
Alarm active, sludge level sensor is covered
with sludge.
flashes
Internal sensor fault, lead breakage or short-
circuit