background image

22

5538

 201

1-

04

12

SAFETY MANUAL SIL KFD0-RSH-1.4S.PS2

Proof Test

4

Proof Test

4.1

Proof Test Procedure

According to IEC 61508-2 a recurring proof test shall be undertaken to reveal 

potential dangerous fails that are otherwise not detected by diagnostic test.
The functionality of the subsystem must be verified at periodic intervals 

depending on the applied PFD

avg

 in accordance with the data provided in see 

chapter 2.4.
It is under the responsibility of the operator to define the type of proof test and the 

interval time period.
The ancillary equipment required:

A digital multimeter (without special accuracy) will be used as ohmmeter 

(mid range recommended) to check the relay outputs. Closed contacts are 

shown with 0 

Ω

 (low impedance), open contacts are shown with OL 

(overload/high impedance).

Power supply set at nominal voltage of 24 V DC

Procedure:

For the proof test five tests have to be done as shown in the following table and 

pictures:

Test No. Input or Test Input

Output (mA)

1

V

test input

 = 24 V DC

between terminals 10+, 11-

DTS output (terminals 5, 6): OL (overload)

ETS output (terminals 2, 3): shows 0 

Ω

Red LED TST1 is flashing.

2

V

test input

 = 24 V DC

between terminals 11-, 12+

DTS output (terminals 5, 6): OL (overload)

ETS output (terminals 2, 3): shows 0 

Ω

Red LED TST2 is flashing.

3

V

test input

 = 24 V DC

between terminals 10+, 11- and

between terminals 11-, 12+

DTS output (terminals 5, 6): shows 0 

Ω

ETS output (terminals 2, 3): shows 0 

Ω

Both red LEDs are flashing.

4

V

test input

 = 0 V DC

between terminals 10+, 11- and

between terminals 11-, 12+

DTS output (terminals 5, 6): OL (overload)

ETS output (terminals 2, 3): OL (overload)

Both red LEDs are off.

5

V

input

 = 24 V DC

between terminals 7+ and 8- and with changed 

input polarity between terminals 7-, 8+

DTS output (terminals 5, 6): shows 0 

Ω

ETS output (terminals 2, 3): shows 0 

Ω

Yellow LED is on.

Table 4.1

 Expected test results for a successful proof test

Summary of Contents for KFD0-RSH-1.4S.PS2

Page 1: ...ISO9001 3 RELAY MODULE KFD0 RSH 1 4S PS2 PROCESS AUTOMATION SAFETY MANUAL SIL ...

Page 2: ...livery for Products and Services of the Electrical Industry published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its most recent version as well as the supplementary clause Expanded reservation of proprietorship SAFETY MANUAL SIL KFD0 RSH 1 4S PS2 ...

Page 3: ...nd Directives 5 2 Planning 6 2 1 System Structure 6 2 1 1 Low Demand Mode 6 2 1 2 High Demand Mode 6 2 2 Assumptions 7 2 3 Safety Function and Safe State 8 2 4 Characteristic Safety Values 9 3 Safety Recommendation 10 3 1 Interfaces 10 3 2 Configuration 10 3 3 Useful Life Time 10 3 4 Installation and Commissioning 11 4 Proof Test 12 4 1 Proof Test Procedure 12 5 Abbreviations 16 ...

Page 4: ...ause damage to property environment or persons for which Pepperl Fuchs GmbH will not be liable The devices are developed manufactured and tested according to the relevant safety standards They must only be used for the applications described in the instructions and with specified environmental conditions and only in connection with approved external devices 1 2 Intended Use This signal conditioner...

Page 5: ...evice specific standards and directives Functional safety IEC 61508 part 1 7 edition 2000 Standard of functional safety of electrical electronic programmable electronic safety related systems product manufacturer Electromagnetic compatibility EN 61326 1 2006 NE 21 2006 System specific standards and directives Functional safety IEC 61511 part 1 3 edition 2003 Standard of functional safety safety in...

Page 6: ...Demand and Tproof proof test interval that has a direct impact on the PFDavg the SFF value Safe Failure Fraction the HFT architecture Hardware Fault Tolerance architecture 2 1 2 High Demand Mode If there is only one loop which combines the standard operation and safety related operation then usually the demand rate for this loop is assumed to be higher than once per year The relevant safety parame...

Page 7: ...appearance of a safe error e g output in safe state would be repaired within 8 hours During the absence of the device for repairing measures have to be taken to ensure the safety function for example substitution by an equivalent device For high currents and high ambient temperature the de rating given in the data sheet needs to be considered The input of the device must be connected to a safety P...

Page 8: ...he DTS output being open not conducting Reaction Time The reaction time is 20 ms ETS Safety Function The safety function of the device is defined Whenever the input of the device is energized the ETS output is conducting Safe State For the ETS safety function the safe state is defined as the ETS output being closed conducting Reaction Time The reaction time is 20 ms DPS The dual pole switching app...

Page 9: ...mand Mode Safety function 2 ETS 4 DTS HFT 0 0 SIL 3 3 λsd λsu 139 7 FIT 144 77 FIT λdd 0 FIT 0 FIT λdu 7 1 FIT 1 83 FIT λtotal safety function 146 6 FIT 146 6 FIT SFF 95 2 98 7 MTBF 3 639 years 560 years PFH 7 1 x 10 9 1 h 1 83 x 10 9 1 h PFDavg for T1 1 year 3 1 x 10 5 8 01 x 10 6 Tproof max 3 years 12 years Reaction time 20 ms 1 Pepperl Fuchs documentation number 2 The device can be used in two ...

Page 10: ...at the useful life time of components is not exceeded Beyond this useful life time the result of the probabilistic calculation is meaningless as the probability of failure significantly increases with time The useful life time is highly dependent on the component itself and its operating conditions temperature in particular for example the electrolytic capacitors can be very sensitive to the worki...

Page 11: ...ice The effective life time can be higher Maximum Switching Power of Output Contacts The useful life time is limited by the maximum switching cycles under load conditions You can see the relationship between the maximum switching power and the load conditions in the diagram below Figure 3 1 3 4 Installation and Commissioning Installation has to consider all aspects regarding the SIL level of the l...

Page 12: ...ge of 24 V DC Procedure For the proof test five tests have to be done as shown in the following table and pictures Test No Input or Test Input Output mA 1 Vtest input 24 V DC between terminals 10 11 DTS output terminals 5 6 OL overload ETS output terminals 2 3 shows 0 Ω Red LED TST1 is flashing 2 Vtest input 24 V DC between terminals 11 12 DTS output terminals 5 6 OL overload ETS output terminals ...

Page 13: ...of Test 225538 2011 04 13 Figure 4 1 Proof test set up for KFD0 RSH 1 4S PS2 test 1 Figure 4 2 Proof test set up for KFD0 RSH 1 4S PS2 test 2 4 5 6 2 3 10 12 11 24 V Multimeter Ω Multimeter Ω 10 12 11 24 V 4 5 6 2 3 Multimeter Ω Multimeter Ω ...

Page 14: ...H 1 4S PS2 Proof Test Figure 4 3 Proof test set up for KFD0 RSH 1 4S PS2 test 3 Figure 4 4 Proof test set up for KFD0 RSH 1 4S PS2 test 4 4 5 6 2 3 24 V 24 V Multimeter Ω Multimeter Ω 10 12 11 4 5 6 2 3 0 V 0 V Multimeter Ω Multimeter Ω 10 12 11 ...

Page 15: ...KFD0 RSH 1 4S PS2 Proof Test 225538 2011 04 15 Figure 4 5 Proof test set up for KFD0 RSH 1 4S PS2 test 5 Only if all tests are successfully done the proof test is successfull 7 4 5 6 2 3 8 24 V Multimeter Ω Multimeter Ω ...

Page 16: ...FDavg Average Probability of Failure on Demand PFH Probability of dangerous Failure per Hour PTC Proof Test Coverage SFF Safe Failure Fraction SIF Safety Instrumented Function SIL Safety Integrity Level SIS Safety Instrumented System Tproof Proof Test Interval DPS Dual Pole Switching DTS De energized To Safe State ESD Emergency Shut Down ETS Energized To Safe State ...

Page 17: ...SAFETY MANUAL SIL KFD0 RSH 1 4S PS2 Notes 225538 2011 04 17 ...

Page 18: ...hs com Worldwide Headquarters Pepperl Fuchs GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com For the Pepperl Fuchs representative closest to you check www pepperl fuchs com pfcontact PROCESS AUTOMATION PROTECTING YOUR PROCESS 225538 TDOCT 2052CENG 04 2011 ...

Reviews: