2
0
2
0
-0
6
46
Commissioning for PROFINET
Writing I&M Records
I&M data can be written using the standard WDREC (SFB53) function block in the TIA portal.
First, the hardware identifier of the CPU is read out under "PLC Variables > System Constants."
The CPU should be displayed there as <Local> with the data type "Hw_SubModule." You spec-
ify the hardware identifier via the corresponding input parameter (ID). The I&M index (INDEX)
and the data length (LEN) to be written must also be transmitted. The return parameters con-
tain a status or an error message.
5.2.10
Prioritized Start-Up/Fast Start-Up (FSU)
The modules with Fast Start-Up (FSU) support optimized system power-up. This ensures a
quick restart after a power supply is restored after an interruption.
Figure 5.27
1.
Select "Device View" (1) and the desired module (in this example, slot 1 for ICE1-8IOL-G60L-
V1D_1).
2.
Then, in the "General" tab, select the "Advanced Options" area (2).
3.
Click on the "Prioritized Start-Up" option (3) to enable prioritized startup.
5.2.11
Resetting Modules to their Factory Settings
To reset the modules to the factory settings, you must search for accessible PROFINET nodes
in the TIA Portal.
1.
Open the dialog "Accessible devices" via the main menu "Online -> Accessible devices ...."
1
2