Commands
2014-
03
29
Configure interface (CI):
This command sets the timeout and the baud rate. The values are stored in the non-volatile
memory of the control unit.
The timeout command indicates the amount of time after which the device no longer waits for
more characters in a command. After the timeout expires, the user receives an error message.
To deactivate the timeout, you must set the time to "0".
The number of data bits is always 8. A parity bit is never used. The following settings are
possible:
The default values are a timeout of "
0
" and a baud rate of "
38400
".
Configuration store (CS):
The configuration store (CS) command allows you to store the last command sent to the R/W
head in the non-volatile memory of the IDENTControl Compact. The R/W head executes the
command automatically again if the power supply is interrupted or the IDENTControl Compact
is reset.
<Mode>='1' activates the mode.
<Mode>='0' deactivates the mode.
Configuration store
is deactivated by default.
Get state (GS):
This command is used to read the device settings stored in the non-volatile memory of the
control interface, which become active after the next reset.
Reset (RS):
This command terminates all active commands. The device settings are reloaded from the
non-volatile memory.
Command:
CI
<Timeout>,<Baud><CHCK><ETX>
Response:
<Status><Ident channel><CHCK><ETX>
Note!
The device settings stored in the non-volatile memory always become active after a reset.
<Timeout>:
"
0
"...
“
100
”
(x 100 ms, timeout in 100 ms steps)
<Baud>:
"1200" ,"2400" , "4800" , "9600" , "19200", "
38400
"
Command:
CS
<Ident channel><Mode><CHCK><ETX>
Response:
<Status><Ident channel><CHCK><ETX>
Command:
GS
<CHCK><ETX>
Response:
<Status><Ident channel> TO:<Timeout> BD:<Baud>
HD1:<Status><TagType> HD2:<Status><TagType>
HD3:<Status><TagType> HD4:<Status><TagType> MM:<OnOff>
TM3:<Ident channel><Trigger mode> TM4:<Ident channel><Trigger
mode><CHCK><ETX>
Command:
RS
<CHCK><ETX>
Response:
2<Ident channel><CHCK><ETX>