Functional Safety HiD2030(SK)

Planning

3

Planning

3.1

System Structure

3.1.1

Low Demand Mode of Operation

If there are two control loops, one for the standard operation and another one 

for the functional safety, then usually the demand rate for the safety loop is assumed to be less 

than once per year.
The relevant safety parameters to be verified are:

the PFD

avg

 value (average 

P

robability of dangerous 

F

ailure on 

D

emand) 

and the T

1

 value (proof test interval that has a direct impact on the PFD

avg

value)

the SFF value (

S

afe 

F

ailure 

F

raction)

the HFT architecture (

H

ardware 

F

ault 

T

olerance)

3.1.2

High Demand or Continuous Mode of Operation

If there is only one safety loop, which combines the standard operation and safety-related 

operation, then usually the demand rate for this safety loop is assumed to be higher 

than once per year.
The relevant safety parameters to be verified are:

the PFH value (

P

robability of dangerous 

F

ailure per 

H

our)

Fault reaction time of the safety system 

the SFF value (

S

afe 

F

ailure 

F

raction)

the HFT architecture (

H

ardware 

F

ault 

T

olerance)

3.1.3

Safe Failure Fraction

The safe failure fraction describes the ratio of all safe failures and dangerous detected failures 

to the total failure rate.
SFF = (

s

 + 

dd

) / (

s

 + 

dd

 + 

du

)

A safe failure fraction as defined in IEC/EN 61508 is only relevant for elements or (sub)systems 

in a complete safety loop. The device under consideration is always part of a safety loop 

but is not regarded as a complete element or subsystem.
For calculating the SIL of a safety loop it is necessary to evaluate the safe failure fraction 

of the elements and subsystems, but not of a single device.
Nevertheless the SFF of the device is given in this document for reference.

Summary of Contents for HiD2030

Page 1: ...ISO9001 2 Functional Safety SMART Transmitter Power Supply HiD2030 SK Manual...

Page 2: ...ion as well as the supplementary clause Expanded reservation of proprietorship Worldwide Pepperl Fuchs Group Lilienthalstr 200 68307 Mannheim Germany Phone 49 621 776 0 E mail info de pepperl fuchs co...

Page 3: ...ction 8 2 3 Interfaces 9 2 4 Marking 9 2 5 Standards and Directives for Functional Safety 9 3 Planning 10 3 1 System Structure 10 3 2 Assumptions 11 3 3 Safety Function and Safe State 12 3 4 Character...

Page 4: ...Functional Safety HiD2030 SK Contents 4 2021 09...

Page 5: ...g Dismounting Disposal The documentation consists of the following parts Present document Instruction manual Manual Datasheet Additionally the following parts may belong to the documentation if applic...

Page 6: ...understood the instruction manual and the further documentation Intended Use The device is only approved for appropriate and intended use Ignoring these instructions will void any warranty and absolve...

Page 7: ...displayed in descending order as follows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This symbo...

Page 8: ...an be monitored via a Fault Indication Board This device mounts on a HiD Termination Board HiD2030 The device provides a fully floating supply to power 2 wire SMART transmitters in the explosion hazar...

Page 9: ...ing connections see datasheet Pepperl Fuchs Group Lilienthalstra e 200 68307 Mannheim Germany Internet www pepperl fuchs com HiD2030 HiD2030SK Up to SIL 2 Note If you design the safety loops in homoge...

Page 10: ...lly the demand rate for this safety loop is assumed to be higher than once per year The relevant safety parameters to be verified are the PFH value Probability of dangerous Failure per Hour Fault reac...

Page 11: ...ssumed For a higher average temperature of 60 C the failure rates must be multiplied by a factor of 2 5 based on experience A similar factor must be used if frequent temperature fluctuations are expec...

Page 12: ...ltage outputs DIP switch settings for HiD2030 The outputs can be configured as 4 mA to 20 mA current output 1 V to 5 V voltage output DIP switch settings for HiD2030SK No user configuration available...

Page 13: ...y function Transfer of the analog signals s 1 109 FIT dd 68 FIT du 51 9 FIT total safety function 1 1 No effect failures are not influencing the safety function and are therefore not included in the S...

Page 14: ...umed that early failures are detected to a huge percentage during the installation and therefore the assumption of a constant failure rate during the useful lifetime is valid However according to IEC...

Page 15: ...heck the safety function to ensure the expected output behavior 4 1 Configuration Configuring the Device The device is configured via DIP switches The DIP switches for setting the safety functions are...

Page 16: ...the characteristic safety values provided See chapter 3 4 It is under the responsibility of the plant operator to define the type of proof test and the interval time period With the following instruc...

Page 17: ...ice to the original settings Figure 5 1 Proof test set up for HiD2030 Set input value mA Mandatory measuring points Output value mA Output value V 20 0 20 0 0 4 5 0 0 1 12 0 12 0 0 4 3 0 0 1 4 0 4 0 0...

Page 18: ...D2030SK HiD2030SK Termination Board 11 14 SL1 8a 7a 12 15 10a 9a SL2 1 4 5a 5b 7 7a 2 5 1a 1b 6 3b Fault 1a 1b 2a 2b 6b Zone 2 Div 2 Zone 0 1 2 Div 1 2 I II mA mA Multimeter mA 24 V DC Multimeter mA 2...

Page 19: ...fect always replace the device with an original device Reporting Device Failure If you use the device in a safety loop according to IEC EN 61508 it is required to inform the device manufacturer about...

Page 20: ...tion not part Probability of failure of components that are not in the safety loop total safety function Probability of failure of components that are in the safety loop HFT Hardware Fault Tolerance M...

Page 21: ...Functional Safety HiD2030 SK Notes 2021 09 21...

Page 22: ...Pepperl Fuchs Quality Download our latest policy here www pepperl fuchs com quality www pepperl fuchs com Pepperl Fuchs Subject to modifications Printed in Germany DOCT 7367...

Reviews: