Functional Safety K*D0-RSH-1.1E.1, HiC5863(Y1)
Product Description
2
Product Description
2.1
Function
General
This signal conditioner provides the galvanic isolation between field circuits and control
circuits.
The energized to safe (ETS) function is permitted for SIL 3 applications.
For testing of the relays, test terminals can be used. The test mode will be indicated by a LED.
KCD0-RSH-1.1E.1, KFD0-RSH-1.1E.1
The device is a relay module that is suitable for safely switching applications of a load circuit.
The device isolates load circuits up to 230 V AC and the 24 V DC control circuit.
The device is mounted on a 35 mm DIN mounting rail according to EN 60715.
HiC5863
The device is a relay module that is suitable for safely switching applications of a load circuit.
The device isolates load circuits up to 30 V and the 24 V control circuit.
This device mounts on a HiC termination board.
HiC5863Y1
The device is a relay module that is suitable for safely switching applications of a load circuit.
The device isolates load circuits up to 230 V AC/30 V DC and the 24 V DC control circuit.
This device mounts on a HiC termination board.
2.2
Interfaces
The device has the following interfaces.
•
Safety-relevant interfaces: input, output (ETS)
•
The test input may
not
be used during normal operation. The test input may be used
for test only.
2.3
Marking
Note
For corresponding connections see datasheet.
Fuchs Group
Lilienthalstraße 200, 68307 Mannheim, Germany
Internet: www.pepperl-fuchs.com
KFD0-RSH-1.1E.1, KCD0-RSH-1.1E.1, HiC5863, HiC5863Y1
Up to SIL 3