Functional Safety HiC2871A
Planning
20
17-
11
11
3.4
Characteristic Safety Values
The characteristic safety values like PFD, PFH, SFF, HFT and T
1
are taken from
the FMEDA report. Observe that PFD and T
1
are related to each other.
The function of the devices has to be checked within the proof test interval (T
1
).
Parameters
Characteristic values
Assessment type
Full assessment
Device type
A
Mode of operation
Low demand mode, high demand mode or
continuous mode
HFT
0
SIL (SC)
3
Safety function
The output is de-energized if the input is in low
condition
s
1
76 FIT
dd
0 FIT
du
0 FIT
total (safety function)
1
76 FIT
no part
197 FIT
SFF
1
1
"No effect failures" and "Annunciation failures" are not influencing the safety function and are therefore not
included in SFF and in the failure rates of the safety function.
100 %
MTBF
2
2
acc. to SN29500. This value includes failures which are not part of the safety function/MTTR = 24 h.
262 years
PFH
3
3
As the
d
failure rate is 0 FIT, the PFD calculation yields a PFD of zero, independent from the proof test
interval.
0 1/h
PFD
avg
for T
1
= 1 year
3
0
Reaction time
4
4
Time between fault detection and fault reaction
< 1 s
Table 3.1
Note!
The characteristic values apply to all modes of operation that can be set on the
device.