FDS/OPC Integration
2
02
0-
11
83
5.10.1
Field Device Handling
The advanced diagnostic module (ADM) classifies the field devices as configured field devices
and unconfigured field devices. See also see chapter 2.2.4. The advanced parameterization
allows for either of the following configured device list actions:
•
Add unconfigured field devices
•
Add new configured field devices
•
Remove configured field devices that are no longer required
Adding an Unconfigured Field Device
In order to add an unconfigured field device, proceed as follows:
1.
Right-click the
Advanced Diagnostic Module
in the project section and choose
Additional
Functions > Advanced Parameterization
.
The advanced parameterization window appears.
2.
Select the segment in the
Device Navigation
section.
The segment window appears.
3.
Select the
Field Devices
tab.
4.
Mark the field devices you intend to add in the
Unconfigured Field Devices
section.
5.
Choose
Add selected Field Device
.
Figure 5.51 Unconfigured field devices section
The new field device is located in the configured field devices list.
6.
Choose
Apply
.
Adding a New Field Device
In order to add a new field device, proceed as follows:
1.
Right-click the
Advanced Diagnostic Module
in the project section and choose
Additional
Functions > Advanced Parameterization
.
The advanced parameterization window appears.
2.
Select the segment in the
Device Navigation
section.
The segment window appears.
Note
For more information on the parameters, see chapter 5.8.