2
013-
01
26
Compact Fieldbus Power Hub,Generic Interface
Appendix
The requirements of the association for standard and control and regulations of the German
chemical industries, defined in the NE21 recommendation, are partly higher compared to the
test levels and failure criteria defined in EN61326-1. For the product qualification, failure criteria
and test levels have been selected, representing always the worst case conditions.
EN61000-4, as a generic standard, defines the test setups for the specific required test for
EN61326-1 and NE21.
Applied standards:
■
CE-Conformity 2004/108/EC
■
EN61000-4, July 2007
■
EN61326-1, October 2006
■
EN55011, March 2007
■
NE21, Mai 2006
Conducted EMC tests:
Immunity
6.3
Referenced Documents
■
Manual: "Using Fuchs fieldbus equipment in Zone 2 hazardous area
environment"
■
Selection table: Conformity of FieldConnex
®
Power Hub modules and Motherboards to
Ex ic
Standard
Type
Test Level
Category
EN 61000-4-2
Electrostatic
discharge, direct
contact
6 kV
A
Electrostatic
discharge, indirect, air
8 kV
A
EN 61000-4-3
Electromagnetic field
radiated, radio
frequency
10 V/m
A
EN 61000-4-4
Fast transients burst
on signal lines
1 kV
A
Fast transients burst
on power lines
2 kV
A
EN 61000-4-5
Slow transient surge
on signal lines
1 kV
B
Slow transient surge
on shielded lines
2 kV
B
EN 61000-4-6
Conducted immunity,
radio frequency
10 V
A
EN 55011
RF conducted
emission
Class A
_
RF radiated emission Class A
_