2
0
1
8
-0
7
14
Installation and Commissioning
3
Installation and Commissioning
In the following section you find information on how to install and commission the multi-
input/output (MIO) device in your fieldbus topology.
3.1
Mounting and Dismounting
Mounting/Dismounting F2D0-MIO*
F2D0-MIO* is designed for panel (wall) mounting.
■
Select mounting material that is suitable for the sub-surface (the wall).
■
Ensure that the mounting material guarantees secure fastening.
■
To attach the device: use 2 fixing screws with a diameter of 6 mm.
■
To dismount the device: Undo the fixing screws and take the device off the wall.
Mounting/Dismounting R8D0-MIO*
R8D0-MIO* is designed for mounting on a 35 mm DIN mounting rail in accordance with
EN 50022.
To dismount the device: Take off the device in reverse order.
Danger!
Danger to life from using damaged or repaired devices.
Using a defective or repaired device can compromise its function and its electrical safety.
■
Do not use a damaged or polluted device.
■
The device must not be repaired, changed or manipulated.
■
If there is a defect, always replace the device with an original device from Fuchs.
Danger!
Explosion hazard from damaged electronic components
Premature wear of electronic components in a device that was previously used in a general
electrical installation can cause sparks that can ignite the surrounding potentially explosive
atmosphere.
Never install devices that have already been operated in general electrical installations in
electrical installations used in combination with hazardous areas!
Mounting the R8D0-MIO* Electronics onto the DIN Mounting Rail
1
Place the R8D0-MIO* on the DIN mounting rail.
2
Use the top hook in order to hook the electronics onto the DIN mounting rail.
3
Move the bottom hook over the lower end of the DIN mounting rail.
4
Tighten the 2 fastening screws to attach the electronics on the DIN mounting rail.
Tightening torque: 0.4 Nm
2
3
4
1