PACTware Multi-Input/Output Device Type Manager
2
0
1
8
-0
7
103
Section "Settings":
The following settings determine the reaction of the device on manufacturer-specific diagnostic
events. For each error type you can determine how to diagnose it and determine the status that
the process value issues in case of the diagnosis:
Diagnostic Parameters in the Online Mode
Section "Measured values":
Only available in the online mode. Visualizes the times and stroke counts for quick
recognition.
This information is available only if breakaway/transit time monitoring or stroke count
monitoring is enabled.
Error Type
Diagnosis
Status that the process
value issues if the assigned
diagnosis is active:
Valve mechanics error
■
None
■
Maintenance
■
Maintenance demand
■
Maintenance alarm
■
Invalid process condition
■
Function check
■
GOOD - OK
■
GOOD - Maintenance
required
■
GOOD - Maintenance
demanded
■
UNCERTAIN -
Maintenance demanded
■
BAD - Maintenance alarm
■
UNCERTAIN - Process-
related, no maintenance
■
BAD - Process-related, no
maintenance
■
BAD - Function check/
local override
■
GOOD - Function check
Valve mechanics warning
Valve wire error
Stroke count limit exceeded
Sensor A wire error
Sensor B wire error
Diagnostic Parameters in the Online Mode
Diagnostic information is displayed additionally in the online mode in order to diagnose issues
or failures in real-time as they occur. Any diagnostic information issued by the DTM is
visualized through a NAMUR NE 107 icon in the following places:
■
Left navigation bar
■
Diagnostics tab
■
Top-level DTM information section "Overall status".