AS-i 3.0 Command Interface
Commands of the Command Interface
4.7
Other commands
4.7.1
Overview of the commands
Values for command
see page
Command
Value
Meaning
Req
Len
Res
Len
IDLE
00
16
no request
2
2
READ_IDI
41
16
read IDI
2
36
WRITE_ODI
42
16
write ODI
34
2
READ_ODI
56
16
read ODI
2
34
SET_OFFLINE
0A
16
set Off-Line_Mode
3
2
SET_DATA_EX
48
16
set Data_Exchange_Active
3
2
REWRITE_DPRAM
1
1.
The command REWRITE_DPRAM is valid only for the use with AS-i 3.0 Module OEM Master.
78
16
rewrite DPRAM
3
3
BUTTONS
75
16
disable push buttons
3
2
FP_PARAM
7D
16
functional Profile Parameter
≥
3
≥
2
FP_DATA
2
2.
There are improved versions of these commands. We don‘t recommend to use the old one any more.
7E
16
functional profile data
≥
3
≥
2
EXT_DIAG
3
3.
The command EXT_DIAG is valid only for the use with AS-i 3.0 PROFIBUS Gateways.
71
16
ExtDiag generation
6
2
RD_EXT_DIAG
4
4.
The command RD_EXT_DIAG is valid only for the use with AS-i 3.0 PROFIBUS Gateways.
7B
16
read ExtDiag Settings
2
7
INVERTER
7C
16
configure inverter slaves
12
4
MB_OP_CTRL_WR_FLAGS
85
16
write flags
≥
5
2
MB_OP_CTRL_RD_FLAGS
86
16
read flags
4
≥
3
RD_MFK_PARAM
59
16
read SEW MFK21 parameter
6
≥
3
MB_OP_CTRL_RESET_CT
89
16
reset control cycle time
2
2
MB_OP_CTRL_RD_PRM
88
16
read control parameter
4
18
MB_OP_CTRL_WR_PRM
87
16
write control parameter
20
2
MB_OP_CTRL_STATUS
83
16
read control status information
2
12
MB_OP_CTRL_CONTROL
82
16
write control status flags
3
2
MB_OP_NAME
72
16
read device name
2
34
MB_OP_READ_SERIAL
76
16
read serial number
2
6
Tab. 4-168.