AS-i 3.0 Command Interface
Command Interface Examples
The permanent parameter for the 16 bit module is written.
This command must be repeated for all 31 A-slaves and all 31 B-slaves. If you
don't connect a slave to an address, write the default value to the master (F
hex
)
as a permanent parameter.
5. Switch Master to Protected Mode.
No result because toggle bit = 0.
Setting the toggle bit:
The master has now been ordered to switch to protected mode.
request: SET_OP_MODE
byte 1
0C
hex
(SET_OP_MODE)
byte 2
00
hex
(T = 0, master 1, single master)
byte 3
00
hex
(= protected mode)
byte 4
00
hex
…
…
byte 12
00
hex
Tab. 5-327.
response
byte 1
00
hex
(or old values)
byte 2
00
hex
(or old values)
…
…
byte 12
00
hex
(or old values)
Tab. 5-328.
request: SET_OP_MODE
byte 1
0C
hex
(SET_OP_MODE)
byte 2
80
hex
(T = 1, master 1, single master)
byte 3
00
hex
(= protected mode)
byte 4
00
hex
…
…
byte 12
00
hex
Tab. 5-329.
response
byte 1
0C
hex
byte 2
80
hex
(T = 1, result = 0)
byte 3
00
hex
(or old values)
…
…
byte 12
00
hex
(or old values)
Tab. 5-330.