T-SERIES

Air Conditioner

t15 Model

INSTRUCTION MANUAL

Summary of Contents for T-Series T15

Page 1: ... 2013 Pentair Equipment Protection 89059119 Rev D P N 10 1008 194 T SERIES Air Conditioner T15 Model INSTRUCTION MANUAL ...

Page 2: ...ER 3 INSTALLATION INSTRUCTIONS 4 Design Data 4 Dimensional Drawing 4 Mounting Cutout Dimensions 5 Components List 5 Wire Diagrams 6 Without Heat 6 With Heat 7 Schematics 8 TEMPERATURE CONTROL 9 Units With heat 9 PRINCIPLES OF OPERATION 9 MAINTENANCE 10 Compressor 10 Inlet Air Filter 10 How To Remove Clean or Install a New Inlet Air Filter 10 Condenser and Evaporator Air Movers 11 Refrigerant Loss ...

Page 3: ...ITY BEFORE MOUNTING THE AIR CONDITIONER TO THE ENCLOSURE Refer to the nameplate for proper electrical current requirements and then connect the power cord to a properly grounded power supply Minimum circuit ampacity should be at least 125 of the amperage shown in the design data section for the appropriate model No other equipment should be connected to this circuit to prevent overloading Operate ...

Page 4: ...e taken to keep it from kinking or being elevated above the exit point of the air conditioner The drain tube must be on a continuous downward slope A slight elevation of the tube could result in secondary trap FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN OVERFLOWING OF THE CONDENSATE DRAIN PAN 6 Refer to top of nameplate for electrical requirements Connect the power cord to a properly grou...

Page 5: ...apacitor Compressor 52 6032 09 52 6032 10 Coil Condenser 15 1001 02 15 1001 02 Coil Condenser Coated 15 1001 01 15 1001 01 Coil Evaporator 15 1001 03 15 1001 03 Compressor 10 1016 82 10 1026 101 Filter Air Reusable 89057626 89057626 Filter Dryer 52 6028 03 52 6028 03 Freeze stat 10 1033 26 10 1033 26 Service Cord 52 6035 140 52 6035 141 Terminal Block 10 1003 03 10 1003 03 Thermal Overload Compres...

Page 6: ... 2013 Pentair Equipment Protection 89059119 6 WIRE DIAGRAMS WITHOUT HEAT ...

Page 7: ... 2013 Pentair Equipment Protection 89059119 7 WITH HEAT ...

Page 8: ... 2013 Pentair Equipment Protection 89059119 8 SCHEMATICS With Heat Without Heat ...

Page 9: ... compressor It takes a minimum of one 1 minute after shut down for the compressor suction and discharge pressures to equalize in order for the air conditioner to restart Operating the air conditioner below the minimum ambient temperature or above the maximum ambient temperatures indicated on the nameplate voids all warranties It is recommended that the warranty section of this manual be read in or...

Page 10: ...essor operating temperature causes automatic shut down of the unit The above described shutdown is symptomatic of a clogged or dirty filter thus causing a reduction in cooling air flow across the surface of the compressor and condenser coil Do not run the air conditioner for extended periods of time with the filter removed Particles of dust lint etc can plug the fins of the condenser coil which wi...

Page 11: ...h air conditioner is thoroughly tested prior to leaving the factory to insure against refrigeration leaks Shipping damage or microscopic leaks not found with sensitive electronic refrigerant leak detection equipment during manufacture may require repair or recharging of the system This work should only be performed by qualified professionals generally available through a local reputable air condit...

Page 12: ...e airflow YES proceed to step 6 NO possible problem Defective thermostat Open motor winding Stuck fan motor Obstructed blades Repair or Replace defective part 6 Carefully check the compressor for operation motor should cause slight vibration and the outer case of the compressor should be warm Is the compressor showing signs of this YES wait 5 minutes then proceed to step 7 NO possible problem Defe...

Page 13: ...t won t run Low line voltage at start Should be 10 rated voltage Compressor motor stuck Bad contactor Bad overload switch Bad run start capacitor Unit blows breakers Undersized breaker fuse or not time delayed Short in system Getting water in enclosure Drain plugged Drain tube kinked Enclosure not sealed allowing humidity in Mounting gasket damaged For additional technical information i e amp draw...

Page 14: ... than fourteen 14 days from the date when Buyer has become aware of such occurrence or where the defect is such that it may cause damage immediately such notice containing a description of how the defect manifests itself Failure to provide such prompt notice to Pentair Equipment Protection shall result in forfeiture of Buyer s rights under this warranty In the event of a warranty claim Buyer is to...

Page 15: ...st Failure Analysis can be provided by Pentair Equipment Protection for warrantable goods at no charge Failure analysis for non warranty repairs are subject to a 100 per hour Engineering charge plus any other incurred testing costs F All returned merchandise must be sent to the following address Pentair Equipment Protection 2100 Hoffman Way Anoka MN 55303 1745 G Credit for accepted returns shall b...

Page 16: ... 2013 Pentair Equipment Protection 89059119 Rev D P N 10 1008 194 Pentair Equipment Protection 2100 Hoffman Way Minneapolis MN 55303 USA 1 763 422 2211 1 763 576 3200 PentairEquipmentProtection com ...