background image

1 / 2

PMKG-LE

Low-ProfiLe end SeaL Kit inStaLLation inStructionS

THERMAL MANAGEMENT SOLUTIONS

EN-RaychemPMKGLE-IM-H54075      01/13

DEScRIpTION

The PMKG-LE is a NEMA Type 4X rated end seal kit designed for 

use with Raychem BTV-CR, BTV-CT, QTVR-CT, LBTV2-CT, and 

KHP-CR parallel heating cables. It is designed to be placed on the 

pipe under the insulation and cladding.
For additional information contact your Pentair Thermal 

Management representative or call (800) 545-6258.

TOOLS REqUIRED

•  Screwdriver 

•  Wire cutters

•  Utility knife

ADDITIONAL MATERIALS REqUIRED

•  One grommet: 

(1)

 

  PMK-GK-10 P/N 222724-000 (Package of ten grommets)
•  Glass cloth tape 
  – GT-66 

Installation temperature above 40°F (4°C)

  – GS-54 

Installation temperature above –40°F ( –40°C)

(1) 

Required for LBTV2 (see step 1)

This component is an electrical device that must be installed 

correctly to ensure proper operation and to prevent shock or fire. 

Read these important warnings and carefully follow all of the 

installation instructions.
•  To minimize the danger of fire from sustained electrical arcing 

if the heat ing cable is damaged or improperly installed, and to 

comply with the requirements of Pentair Thermal Management, 

agency certifications, and National Electrical Codes, ground-

fault equipment protection must be used. Arcing may not be 

stopped by conven tion al circuit breakers.

•  Component approvals and performance are based on the use of 

Pentair Thermal Management-specified parts only. Do not use 

substitute parts or vinyl electrical tape.

•  The black heating cable core is conductive and can short. It 

must be properly insulated and kept dry.

•  Damaged bus wires can overheat or short. Do not break bus wire 

strands when scoring the jacket or core.

•  Keep components and heating cable ends dry before and during 

installation.

•  Bus wires will short if they contact each other. Keep bus wires 

separated.

•  Use only fire-resistant insulation materials, such as fiberglass 

wrap or flame-retardant foam.

WARNING:

KIT cONTENTS

Item qty  Description

Pressure plate

End seal body with stainless steel screws

Red grommet (not for use with LBTV2)

End seal label

A

B

C

D

AppROvALS

-W

Class I, Div. 2, Groups A, B, C, D

Class II, Div. 2, Groups F, G

Class III

KHP-CR heating cables only

Hazardous Locations

Nonhazardous Locations

BTV-CR, BTV-CT, QTVR-CT and LBTV2-CT heating cables only

Reviews: