Pentair PPC5 Series Quick Start Manual Download Page 1

About

 

The PENTEK Pump Controller (PPC5) is pre-jumpered 
and programmed with the PENTEK Assistant, providing 
ease of setup for constant pressure applications. The 
PENTEK Assistant defaults to pre-defined parameters 
as described in this guide, and also prompts the user for 
application-specific information.
This guide covers the startup of the PENTEK Assistant 
for constant pressure applications. For other programs, 
refer to the ABB manual provided. 

SAfety

Hazardous voltage. Can shock, burn, or 

cause death. Ground pump before connecting to power 

supply. Disconnect power before working on system  

components.

Wire pump motor for correct voltage. See motor 

nameplate.

Ground motor to drive before connecting to 

power supply.

Meet National electri cal Code, Canadian elec tri cal 

Code, and local codes for all wiring.

California Proposition 65 Warning

 This product and related accessories contain 

chemicals known to the State of California to cause 
cancer, birth defects or other reproductive harm.

INStAllAtIoN

Connect transducer
Install the transducer where pressure is to be maintained.  
The PENTEK Assistant requires a 4 - 20 ma transducer 
(Figure 2). The transducer’s power lead should be 
attached to terminal 10 or the terminals as shown below 
and the 4 - 20 ma output lead should be attached to ter-
minal 5 (Figure 3). The transducer has a brown power 
lead and a blue 4 - 20 ma output lead.  
(All jumper terminals may need to be loosened to attach 
leads above the jumper board).   
The jumper board eliminates the need to hand wire termi-
nals 9 to 11, 10 to 19, 11 to 12 and 18 to 21.
Before applying power, make sure the front cover is on 
and the control module is in place.

Startup the PENTEK Assistant
Apply power to the unit, and follow the steps on Pages 2 
and 3 after the controller’s screen is lit. 

EXIT

00:00

SAVE

REM

PAR   EDIT

3.0  hp

9909 MOTOR NOM POWER

Scroll

Buttons

Controller Mode

PID Address 
andFunction 
Description 

Value 

Right Button

Right Button
Function

Left Button

Left Button 

Function

Motor Rotation

Indicator

Help

Local / 

Remote

Start

Stop

Local / Remote 

Indicator

fIGuRe 1: Control Panel button location

4 - 20 ma Output

Jumper Board

Power Lead

DIP Switches

+24 volt
Power 
Connection

fIGuRe 3: transducer connection to terminal strip

fIGuRe 2: transducer and Cable

Transducer cable

Transducer

QUICK START GUIDE

PPC5 Series

Pump Controller

© 2012 Pentair, Inc. All Rights Reserved. 

PN770 (11/08/12)

293 WRIGHT STREET, DELAVAN, WI 53115  WWW.PUMPS.COM
PH: 1-866-9 PENTEK

Summary of Contents for PPC5 Series

Page 1: ...ucer Figure 2 The transducer s power lead should be attached to terminal 10 or the terminals as shown below and the 4 20 ma output lead should be attached to ter minal 5 Figure 3 The transducer has a...

Page 2: ...o select the speed and press SAVE The sample here shows 3450 RPM 6 EXIT 00 00 SAVE REM PAR EDIT 3450 rpm 9908 MOTOR NOM SPEED range 0 10 bar 145 psi max pressure 25 bar 362 5 psi UE 80 330 VDC OUT 4 2...

Page 3: ...the PID sleep func tion will be enabled This is a controller assigned value For additional information refer to the ACS550 Users Manual Scroll to select the speed and then press SAVE The sample here...

Page 4: ...EL 19 Internal 4011 INTERNAL SETPOINT USER DEFINED 4016 ACT1 INPUT 1 AI2 4017 ACT2 INPUT 1 AI2 4022 SLEEP SELECTION 7 INT 4024 PID SLEEP DELAY 10 SEC 4027 PID 1 PARAM SET 3 DI3 4102 INTEGRATION TIME 1...

Page 5: ...ive to restart For example if the set point is 60 PSI and the Wake Up Deviation is 10 PSI the drive will restart at 50 PSI Timer Function The Pentek VFD includes four timer functions Each timer functi...

Page 6: ...ations Multiple Systems Setpoints The Pentek VFD includes 2 independent process con trol sets groups 40 and 41 Group 41 parameters can be selected using Digital Input DI3 When first set up groups 40 a...

Page 7: ...__________________ Motor Model _________________________________________________ Motor Nominal Voltage ________________________________________ Motor Nominal Current __________________________________...

Page 8: ...roduct in water under 86 F with proper flow conditions cooling the motor parameter 3007 can be set to 112 Submersible motors should always operate within its ser vice factor limit Program Change Set P...

Reviews: