6.2. Volumetric
6.2.1. Calculating the system capacity
Set the capacity of soft water between two regenerations using the following formula:
Water capacity [m
3
] = (Exchange capacity [m
3
°tH] - Reserve capacity [m
3
]) / Water hardness [°tH]
1. 24 hour wheel
2. Available
capacity
→ Shows the system remaining capacity.
3. Program
wheel
→ Defines the system capacity in m
3
.
4. Time of day
→ Shows the current time.
5. Service
position
→ Service;
→ Regeneration;
→ Backwash;
→ Brine draw/slow rinse;
→ Brine refill.
6. Red
lamp
→ Lights when the valve regenerate.
7. Green
lamp
→ Lights when in service.