Installer manual Fleck 2850 SXT - Programming
56 / 104
Ref. MKT-IM-030 / C - 12.05.2020
6.5.6
Number of tanks (NT)
Select the number of tanks.
Options:
• NT 1: single tank system;
• NT 2: double tanks system.
Mandatory
Due to the 2850 valve being designed for single tank system only, set valve type to 1.
1. Press
or
until "---1" is displayed.
2. Press
to validate the selection and move to the next parameter.
6.5.7
Tank in service (TS)
Info
This parameter appears only if number of tanks (NT) is set to 2.
If it appears, the 2850 valve being a single tank system, go back to number of tanks (
NT
)
and set it to 1.
6.5.8
Unit capacity (C)
Set the unit capacity.
Mandatory
Enter the capacity of the media bed in m
3
x °TH or g as CaCO
3
for softener system (C is
displayed in the upper left corner) or in litres for filter (V is displayed in the upper left
corner) !
Info
The unit capacity parameter is only available if the controller type has been
programmed for volumetric regeneration.
The unit capacity can be set from 0.1 to 9999 x 1000 °TH*m
3
, g as CaCO
3
equivalent or in
grains if DF=GAL.
1. Press
or
to select the unit capacity.
2. Press
to validate the selection and to move the next parameter.