Installer manual Fleck 2850 SXT - Programming
Ref. MKT-IM-030 / C - 12.05.2020
51 / 104
6.2
Commands
Info
Menus are displayed in a defined and incremental order.
If none of the buttons are pushed for 5 minutes in the Programming mode, or if there is
a power failure, the controller returns to Service mode without saving.
Mandatory
In order to store the new settings in the programming mode, it is necessary to go
through all the parameters !
1. Press
to pass to the next step.
2. Use
and
to adjust the values.
6.3
Setting the time of the day (TD)
Set the time in the system.
1. Press and hold
or
until the programming icon replaces the
service icon and the parameter display reads TD.
2. Set the time with
or
.
3. Press
to validate the selection and return to the service mode, or wait
for 10 seconds.
6.4
Basic programming
6.4.1
Basic programming mode chart
Parameter
Options
Definition
Note
DO
Days override
0 to 99
Day
-
RT
Regeneration
time
00:00:00 to
23:59:59
Hour
Regeneration time will not appear
unless regeneration day override is
on.
H
Feedwater
hardness
1 to 1990
°TH, ppm or
grains
Only displayed for volumetric
regenerations.
RC
Fixed reserve
capacity
0 to 50
%
Only displayed for volumetric
regenerations and if set in reserve
selection.
SF
Safety factor
0 to 50
%
Only available if set in reserve
selection.
CD
Current day
1 to 7
Day of the week
-