Pentair 962 Series Operation Manual Download Page 1

TIME OF DAY

TIME OF REGEN

HARDNESS

CAPACITY

REGEN TIME

REMAINING

SET

REGEN

SERIES 962

FLOW

PM

Operation Manual

Series 962

Electronic Stager Control

Summary of Contents for 962 Series

Page 1: ...TIME OF DAY TIME OF REGEN HARDNESS CAPACITY REGEN TIME REMAINING SET REGEN SERIES 962 FLOW PM Operation Manual Series 962 Electronic Stager Control...

Page 2: ...2...

Page 3: ...splay Programming the Series 962 Stager 7 Factory Default Values Program Levels Level I Programming Setting Time of Day Level II Programming Changing a Program Value Level III Programming Level IV Pro...

Page 4: ...equipment is not supplied with built in overcurrent protection fuses or circuit breakers An external switch and or circuit breaker must be installed by a qualified electrician in accordance with all...

Page 5: ...nal Input TB2 Terminal 17 Delayed Start Input Dry Contact TB2 Terminal 18 Delayed Start Input Dry Contact TB2 Terminal 19 Lockout Input Dry Contact TB2 Terminal 20 Lockout Input Dry Contact Outputs Te...

Page 6: ...150 or more Capacity Setting Lockout The control can be programmed to lock the capacity so it cannot be altered after installation Selectable Reserve Options To meet the application requirements the c...

Page 7: ...ing battery power the display will alternate between Time of Day and Capacity Remaining once power has been restored The control will remain in this display mode until the Time of Day is reset or unti...

Page 8: ...the new entry is stored and the control automatically scrolls to the next P value If a beep sounds the new entry was not accepted Table 1 lists the range available for a specific program value Level...

Page 9: ...regeneration This signal can also come from external equipment that can provide a dry contact closure CONNECTION MUST BE A DRY CONTACT NOTE When using the Relay Output Option the lockout feature cann...

Page 10: ...capacity of zero gallons and override the Time of Regeneration P2 to allow for an immediate regeneration These are the preferred settings for a Twin Alternating softener system Advance Cycle Function...

Page 11: ...6 or 9 Do not program P10 P11 Rinse time 1 19 1 4 minutes If P17 6 or 9 Do not program P11 P12 Units of measure 0 1 1 0 0 US 1 Metric P13 Clock mode 0 1 1 0 0 12 hour clock 1 24 hour clock P14 Calend...

Page 12: ...eset L 5 0 655360 0 6553 6 Water used today in gallons M3 since time of regeneration L 6 0 655360 0 6553 6 Water used since last regeneration in gallons M3 L 7 0 655360 0 6553 6 Average water usage fo...

Page 13: ...12 Cycle Time 0 min 255 min 1 min 0 Stager Cycle P17 6 or 9 C13 Position 13 Cycle Time 0 min 255 min 1 min 0 Stager Cycle P17 6 or 9 C14 Position 14 Cycle Time 0 min 255 min 1 min 0 Stager Cycle P17...

Page 14: ...on 4 Cycle Time P5 Capacity of unit C5 Position 5 Cycle Time P6 Not used C6 Position 6 Cycle Time P7 Not used C7 Position 7 Cycle Time P8 Not used C8 Position 8 Cycle Time P9 Backwash time C9 Position...

Page 15: ...controller When using a model 58 TA the Tank in Service is indicated by two NEMA 4 rated door mounted lights that are operated by the stagers second auxiliary switch When using a model 58 TA Twin Alt...

Page 16: ...ced between terminals 1 and 3 and 2 and 4 For 230VAC jumpers are placed between terminals 2 and 3 only Figure 5 Line voltage and neutral inputs are always on terminals 1 and 4 respectively Figure 5 Fl...

Page 17: ...ds that the remote input signal will be ignored before starting a regeneration THE CONNECTION MUST BE A NO VOLTAGE DRY CONTACT Figure 8 Remote Regeneration Start Connections Relay Output Option A sing...

Page 18: ...18 Figure 10 E948 E951 Standard Wiring Design...

Page 19: ...19...

Page 20: ...2009 Pentair Residential Filtration LLC P N 1076301 Rev H FE09...

Reviews: