DRAINAGE PIPE/TRAP DETAIL
Drainage ports provided on the fan housing provide drainage for the system. It is recommended that these drains are piped to allow
proper drainage of any condensation collected in the unit.
1. Drain connections are 3/4 inch NPT.
2. Drain piping installed must have proper slope.
3. P traps are to be filled to proper level prior to unit start up.
Positive Pressure Trap on Tubular Fan Housing
N = Fluid displacement based on system pressure (field determined)
H = N + (1.25" minimum)
H/2
H/2
H
1.25 inch
minimum
N
FAN ON
FAN OFF
Connect
this end
to fan drain.